Computational Analysis of Single-Sided Ventilation for a Cubic Room in Dhaka City with the Influence of Solar Radiation

DOI: 10.4236/ijmnta.2025.144005, PP. 74-95

Keywords: Natural Ventilation, Solar Radiation, CFD, FEM, Turbulence Model

Full-Text   Cite this paper   Add to My Lib

Abstract:

Energy consumption in Bangladesh has been increasing day by day due to population growth, industrial, and technological development. In accordance with the annual report of the Bangladesh Power Development Board (BPDB), the domestic sector is the largest energy-consuming sector in Bangladesh. The average monthly temperature of Dhaka city is moving forward, according to the Bangladesh Meteorological Department. The rising numbers of different electrical appliances for cooling are responsible for this large energy consumption. In a living room, solar radiation has an essential influence on the heat balance in several ways. So, the use of natural ventilation with solar radiation in buildings is now a demand of the time. This study aims to examine the wind profiles and temperature distributions inside and outside the building to understand the indoor air quality as well as thermal comfort. In this research, a single room with single/double opening(s) on the windward wall and the leeward wall with the effect of solar radiation have been studied by using Computational Fluid Dynamics (CFD) based on the Finite Element Method (FEM). The standard k-ε turbulence model has been used in the present investigation on wind-driven natural ventilation with a three-dimensional room for four physical models, which have been calculated in the context of weather in Dhaka city. The physical model has been solved by the commercial software COMSOL Multiphysics. Based on wind direction, the output of airflow, ventilation rate, and average room temperature inside the room are approximately 0.4 m/s, 5.4 × 10?4 m3/s and 300 K, respectively. The radiosity of the computational domain is in the range from 353 to 405 at noon. All values are satisfied with the ASHRAE standard for all configurations. Based on the data of air quality and the volume average temperature, double openings in the windward wall are more comfortable than the other openings. This outcome can open a new dimension in the field of an energy-efficient building to live healthily and reduce the consumption of the mechanical system and also help the designer to design buildings for considering the environmental parameters to build an energy-efficient city.

References

[1]  International Energy Agency (2013) World Energy Outlook 2013.
[2]  Kusuda, T. (1977) Fundamentals of Building Heat Transfer. Journal of Research of the National Bureau of Standards, 82, 97-106.
https://doi.org/10.6028/jres.082.008
[3]  Jiang, Y., Alexander, D., Jenkins, H., Arthur, R. and Chen, Q. (2003) Natural Ventilation in Buildings: Measurement in a Wind Tunnel and Numerical Simulation with Large-Eddy Simulation. Journal of Wind Engineering and Industrial Aerodynamics, 91, 331-353.
https://doi.org/10.1016/s0167-6105(02)00380-x
[4]  Allocca, C., Chen, Q. and Glicksman, L.R. (2003) Design Analysis of Single-Sided Natural Ventilation. Energy and Buildings, 35, 785-795.
https://doi.org/10.1016/s0378-7788(02)00239-6
[5]  Jiang, Y. and Chen, Q. (2003) Buoyancy-Driven Single-Sided Natural Ventilation in Buildings with Large Openings. International Journal of Heat and Mass Transfer, 46, 973-988.
https://doi.org/10.1016/s0017-9310(02)00373-3
[6]  Seifert, J., Li, Y., Axley, J. and Rösler, M. (2006) Calculation of Wind-Driven Cross Ventilation in Buildings with Large Openings. Journal of Wind Engineering and Industrial Aerodynamics, 94, 925-947.
https://doi.org/10.1016/j.jweia.2006.04.002
[7]  Evola, G. and Popov, V. (2006) Computational Analysis of Wind Driven Natural Ventilation in Buildings. Energy and Buildings, 38, 491-501.
https://doi.org/10.1016/j.enbuild.2005.08.008
[8]  Larsen, T.S. and Heiselberg, P. (2008) Single-sided Natural Ventilation Driven by Wind Pressure and Temperature Difference. Energy and Buildings, 40, 1031-1040.
https://doi.org/10.1016/j.enbuild.2006.07.012
[9]  Bangalee, M.Z.I., Lin, S.Y. and Miau, J.J. (2012) Wind Driven Natural Ventilation through Multiple Windows of a Building: A Computational Approach. Energy and Buildings, 45, 317-325.
https://doi.org/10.1016/j.enbuild.2011.11.025
[10]  Montazeri, H. and Blocken, B. (2013) CFD Simulation of Wind-Induced Pressure Coefficients on Buildings with and without Balconies: Validation and Sensitivity Analysis. Building and Environment, 60, 137-149.
https://doi.org/10.1016/j.buildenv.2012.11.012
[11]  Idris, A. and Huynh, B.P. (2013) Analysis of Single-Sided Ventilated Room with Different Location of Windows Opening Using CFD. Congress of Numerical Methods in Engineering, Bilbao, 25-28 June 2013, 1-17.
[12]  Gendelis, S. and Jakovics, A. (2007) Influence of Solar Radiation and Ventilation Conditions on Heat Balance and Thermal Comfort Conditions in Living-Rooms. Proceedings of 5th Baltic Heat Transfer Conference, Saint-Petersburg, 19-21 September 2007, 634-643.
[13]  Bangladesh Power Development Board (2019) Annual Report 2018-2019.
[14]  Ahmmad, M.R. (2014) Statistical Analysis of the Wind Resources at the Importance for Energy Production in Bangladesh. International Journal of u- and e-Service, Science and Technology, 7, 127-136.
https://doi.org/10.14257/ijunesst.2014.7.2.12
[15]  Hossain, M., Bhuiya, M.R. and Al-Mamun, M.M. (2014) An Analysis of the Temperature Change of Dhaka City. Proceedings of 5th International Conference on Environmental Aspects of Bangladesh, Dhaka, 4-5 September 2014, 46-48.
[16]  Eftekhari, M.M., Marjanovic, L.D. and Pinnock, D.J. (2003) Air Flow Distribution in and around a Single-Sided Naturally Ventilated Room. Building and Environment, 38, 389-397.
https://doi.org/10.1016/s0360-1323(02)00016-1
[17]  Ayad, S.S. (1999) Computational Study of Natural Ventilation. Journal of Wind Engineering and Industrial Aerodynamics, 82, 49-68.
https://doi.org/10.1016/s0167-6105(98)00210-4
[18]  Chen, Q. and Srebric, J. (2000) Application of CFD Tools for Indoor and Outdoor Environment Design. International Journal on Architectural Science, 1, 14-29.
[19]  Sharma, A. (2021) Introduction to CFD: Development, Application, and Analysis. In: Introduction to Computational Fluid Dynamics, Springer, 19-33.
https://doi.org/10.1007/978-3-030-72884-7_2
[20]  Gan, G. (2000) Effective Depth of Fresh Air Distribution in Rooms with Single-Sided Natural Ventilation. Energy and Buildings, 31, 65-73.
https://doi.org/10.1016/s0378-7788(99)00006-7
[21]  Visagavel, K. and Srinivasan, P.S.S. (2009) Analysis of Single Side Ventilated and Cross Ventilated Rooms by Varying the Width of the Window Opening Using CFD. Solar Energy, 83, 2-5.
https://doi.org/10.1016/j.solener.2008.06.004
[22]  Chen, Q. (2004) Using Computational Tools to Factor Wind into Architectural Environment Design. Energy and Buildings, 36, 1197-1209.
https://doi.org/10.1016/j.enbuild.2003.10.013
[23]  Spengler, J.D., Samet, J.M. and McCarthy, J.F. (2001) Chap. 59. Indoor Air Quality Handbook. In: Chen, Q. and Glicksman, L.R., Eds., Application of Computational Fluid Dynamics for Indoor Air Quality Studies, McGraw-Hill, 16-17.
[24]  Yakhot, V., Orszag, S.A., Thangam, S., Gatski, T.B. and Speziale, C.G. (1992) Development of Turbulence Models for Shear Flows by a Double Expansion Technique. Physics of Fluids A: Fluid Dynamics, 4, 1510-1520.
https://doi.org/10.1063/1.858424
[25]  Rahman, M.H. and Islam, A.K.M.S. (2010) CFD Modelling of Natural and Forced Ventilation System in a Conventional Kitchen in Bangladesh. The 13th Asian Congress of Fluid Mechanics, Dhaka, 17-19 December 2010, 460-464.
[26]  ASHRAE (2010) ASHRAE Standard 55-2010. Thermal Environment Standards for Human Occupancy.