False Alarm Prevention System for Automatic Fire Shutters in Cold Storage: Focusing on Air Sampling and Waterproof Fixed Temperature Detectors

DOI: 10.4236/jbcpr.2026.142006, PP. 115-131

Keywords: Cold Storage, Automatic Fire Shutter, False Alarm, Air Sampling Detector (ASD), Water Trap

Full-Text   Cite this paper   Add to My Lib

Abstract:

This study investigates the prevention of false alarms in automatic fire shutter systems within cold storage warehouses, which are frequently triggered by condensation and frost. Despite the advancement of fire safety regulations from basic smoke and heat detectors to photoelectric and flame-type sensors, the high-humidity and low-temperature environments of cold storage facilities still present significant reliability challenges. To address these issues, this paper proposes a hybrid interlock system that utilizes an Air Sampling Detector (ASD) as the first-stage trigger and a Waterproof Fixed Temperature Detector as the second-stage trigger. The proposed ASD system incorporates a dedicated water trap designed to effectively separate and remove moisture from the sampled air, thereby preventing sensor malfunctions caused by water droplets. In smoke response tests on five sampled units, fire signals were transmitted within 15 - 32 s, well below the 120 s maximum transport time. During a 105-day field monitoring period, 19 of the 20 installed ASDs recorded no false alarms, and the single false alarm was traced to an improper sensitivity setting rather than condensation, whereas 12 false alarms caused by condensation and frost occurred in adjacent areas equipped with conventional spot-type smoke detectors. However, the second-stage spot-type heat detectors were mounted at a ceiling height of approximately 10 m, which exceeds the 8 m limit for spot-type heat detectors under the Korean fire detection code (NFTC 203); their role in this study is therefore limited to demonstrating environmental durability, and regulatory compliance of the second stage at high ceilings remains an open issue. These findings suggest that the proposed first-stage ASD can improve the operational reliability of fire shutters in specialized logistics environments.

References

[1]  Foster, A.M., Swain, M.J., Barrett, R.V. and James, S.J. (2003) Experimental Verification of Analytical and CFD Predictions of Infiltration through Cold Store Entrances. International Journal of Refrigeration, 26, 918-925.
https://doi.org/10.1016/s0140-7007(03)00097-5
[2]  Fire Industry Association (2012) Guidance Note: Design, Installation, Commissioning and Maintenance of Aspirating Smoke Detector (ASD) Systems. Version 1, Fire Industry Association.
[3]  Nam, G.S. (2016) A Study for the Unity of Construction and Supervision in the Performance Recognition of Fire Protection Facilities. Master’s Thesis, Graduate School of Industrial Environment, Gachon University, 34. (In Korean)
[4]  Roh, H.G. (2011) A Study on the Method of Calculating Fire Detection Time Considering Photoelectric Smoke Detection Characteristics. Ph.D. Dissertation, Kyonggi University, 15-16. (In Korean)
[5]  National Institute of Fire Service (2023) National Fire Safety Technical Standard for Warehouse Facilities (NFTC 609). National Institute of Fire Service Notice No. 2023-46. (In Korean)
[6]  National Fire Agency (2024) Technical Standards for Type Approval and Inspection of Detectors. National Fire Agency Notice No. 2024-11, Article 3. (In Korean)
[7]  Loepfe, M., Ryser, P., Tompkin, C. and Wieser, D. (1997) Optical Properties of Fire and Non-Fire Aerosols. Fire Safety Journal, 29, 185-194.
https://doi.org/10.1016/s0379-7112(96)00048-3
[8]  Ministry of Land, Infrastructure and Transport (2024) Enforcement Regulation of the Act on the Fire Safety Management of Buildings (Criteria for Evacuation and Fire Protection Structures of Buildings). Article 14-4, Criteria for Automatic Fire Shutters. (In Korean)
[9]  National Institute of Fire Service (2024) National Fire Safety Technical Standard for Automatic Fire Detection System and Visual Alarm System (NFTC 203). National Institute of Fire Service Notice No. 2024-1. (In Korean)

Full-Text

Contact Us

service@oalib.com

QQ:3279437679

WhatsApp +8615387084133