Determination of Total Vector Error of the Phasor Measurement Unit (PMU) Using the Phase Angle Error of a Constant Amplitude Voltage Signal

DOI: 10.4236/jpee.2024.1211002, PP. 34-47

Keywords: Phasor Measurement Unit (PMU), Phase Angle Error, Total Vector Error (TVE), State estimation, Time Source Error, Constant Amplitude Signal

Full-Text   Cite this paper   Add to My Lib

Abstract:

This paper investigates the effect of the Phase Angle Error of a Constant Amplitude Voltage signal in determining the Total Vector Error (TVE) of the Phasor Measurement Unit (PMU) using MATLAB/Simulink. The phase angle error is measured as a function of time in microseconds at four points on the IEEE 14-bus system. When the 1 pps Global Positioning System (GPS) signal to the PMU is lost, sampling of voltage signals on the power grid is done at different rates as it is a function of time. The relationship between the PMU measured signal phase angle and the sampling rate is established by injecting a constant amplitude signal at two different points on the grid. In the simulation, 64 cycles per second is used as the reference while 24 cycles per second is used to represent the fault condition. Results show that a change in the sampling rate from 64 bps to 24 bps in the PMUs resulted in phase angle error in the voltage signals measured by the PMU at four VI Measurement points. The phase angle error measurement that was determined as a time function was used to determine the TVE. Results show that (TVE) was more than 1% in all the cases.

References

[1]  Muhayimana, O. and Toman, P. (2022) A Review on Phasor Measurement Units and Their Applications in Active Distribution Networks. 2022 IEEE PES/IAS PowerAfrica, Kigali, 22-26 August 2022, 1-5.
[2]  Chenine, M. and Nordström, L. (2017) Investigation of Communication Delays and Data Incompleteness in Multi-PMU Wide Area Monitoring and Control Systems. 2009 International Conference on Electric Power and Energy Conversion Systems, (EPECS), Sharjah, 10-12 November 2009, 1-6.
[3]  Sharmaa, R.B. and Dholeb, G.M. (2016) Wide Area Measurement Technology in Power Systems. Procedia Technology, 25, 718-725.
[4]  Liao, J.P. and He, C. (2014) Wide-Area Monitoring Protection and Control of Future Power System Networks. 2014 IEEE Workshop on Advanced Research and Technology in Industry Applications (WARTIA), Ottawa, 29-30 September 2014, 903-905.
https://doi.org/10.1109/wartia.2014.6976419
[5]  Singh, R.S., Hooshyar, H. and Vanfretti, L. (2015) Assessment of Time Synchronization Requirements for Phasor Measurement Units. 2015 IEEE Eindhoven PowerTech, Eindhoven, 29 June-2 July 2015, 1-6.
[6]  Koshy, S., Sunitha, R. and Cherian, E.P. (2018) A PMU Model for Dynamic State Estimation of Power Systems. 2018 2nd International Conference on Power, Energy and Environment: Towards Smart Technology (ICEPE), Shillong, 1-2 June 2018, 1-6.
[7]  Agustoni, M., Castello, P., Frigo, G. and Gallus, G. (2023) Time Synchronization Sensitivity in SV-Based PMU Consistency Assessment. Metrology, 3, 99-112.
https://doi.org/10.3390/metrology3010006
[8]  Zhang, J., Tang, C., Liu, C., Wang, H., Duan, J.F. and Tang, S.H. (2023) Phasor Measurement Method Based on Soft Synchronized Sampling with Temporal Pulse Signal Reference. Frontiers in Energy Research, 11, Article ID: 1302869.
[9]  Raikwal, S. (2015) Wide Area Monitoring, Control and Protection of Power System. International Journal of Computer Applications, No. 3, 18-21.
[10]  Björkhem, F., Boivie, J., Jolhammar, M.T. and Nour, O.M. (2024) Implementation of a Phasor Measurement Unit in MATLAB. Department of Electrical Engineering, Uppsala University.
[11]  Bart, Q. and Tzoneva, R. (2018) An FPGA-Based Implementation of a Hilbert Filter for Real-Time Estimation of Instantaneous Frequency, Phase and Amplitude of Power System Signals. International Journal of Applied Engineering Research, 13, 16333-16341.
[12]  Raju, V.V.R., Shree, K.H.P. and Kumar, S.V.J. (2021) Development of Cost-Effective Phasor Measurement Unit for Wide Area Monitoring System Applications. International Journal of Electrical and Computer Engineering (IJECE), 11, 4731-4739.
https://doi.org/10.11591/ijece.v11i6.pp4731-4739
[13]  Castello, P., Muscas, C., Pegoraro, P.A. and Sulis, S. (2018) A Monitoring System Based on Phasor Measurement Units with Variable Reporting Rates. Acta IMEKO, 7, 62-69.
[14]  Blood, E.A., Krogh, B.H. and Ilic, M.D. (2008) Electric Power System Static State Estimation through Kalman Filtering and Load Forecasting. 2008 IEEE Power and Energy Society General MeetingConversion and Delivery of Electrical Energy in the 21st Century, Pittsburgh, 20-24 July 2008, 1-6.
https://doi.org/10.1109/pes.2008.4596742
[15]  Huang, Y., Werner, S., Huang, J., Kashyap, N. and Gupta, V. (2012) State Estimation in Electric Power Grids: Meeting New Challenges Presented by the Requirements of the Future Grid. IEEE Signal Processing Magazine, 29, 33-43.
https://doi.org/10.1109/msp.2012.2187037
[16]  Femine, A.D., Gallo, D., Landi, C. and Luiso, M. (2019). A Design Approach for a Low-Cost Phasor Measurement Unit. 2019 IEEE International Instrumentation and Measurement Technology Conference (I2MTC), Auckland, 20-23 May 2019, 1-6.
https://doi.org/10.1109/i2mtc.2019.8826889
[17]  Ponnala, R., Chakravarthy, M. and Lalitha, S.V.N.L. (2022) Effective Monitoring of Power System with Phasor Measurement Unit and Effective Data Storage System. Bulletin of Electrical Engineering and Informatics, 11, 2471-2478.
https://doi.org/10.11591/eei.v11i5.4085
[18]  Jain, A., Bhardwaj, A., Kumar, S. and Bhullar, S. (2018) Implementation Techniques for Frequency & Phasor Estimation in Phasor Measurement Units (PMUs). 2018 3rd International Conference on Internet of Things: Smart Innovation and Usages (IoT-SIU), Bhimtal, 23-24 February 2018, 1-6.
[19]  Ren, J. and Kezunovic, M. (2011) Real-time Power System Frequency and Phasors Estimation Using Recursive Wavelet Transform. IEEE Transactions on Power Delivery, 26, 1392-1402.
https://doi.org/10.1109/tpwrd.2011.2135385