变电站用380 V负荷支路故障越级跳闸防治措施研究
|
Abstract:
部分站用变配电线路中常出现越级跳闸的问题,造成停电范围扩大,严重威胁供电可靠性,本文首先分析了造成继电保护越级跳闸原因,包括支路保护整定设置不当、上下级保护配合不合理、断路器等元器件故障等,进而对继电保护整定原则和级间配合进行了改进分析,并设计了零序电流保护与脱扣器结合的继电保护方案,现场实验结果表明,该方案可有效解决越级跳闸问题,避免了停电范围扩大及其带来的繁重检修任务,提高供电可靠性。
Over-level tripping often occurs in some substations of electric distribution grid, which may cause and expand power outages and seriously threaten the reliability of power supply. This paper ana-lyzes the causes of the relay protection tripping, including improper setting of branch protection; unreasonable protection coordination between upper and lower levels; failure of components such as circuit breakers etc. Then, a novel relay protection scheme combining zero-sequence current protection and trip unit is designed to improve the setting arrangement and inter-stage cooperation of the relay protection. Field test results show that the scheme proposed by this paper can effectively solve the problem of over-level tripping, and avoid the expansion of power outage and the heavy maintenance tasks brought by it. It can effectively improve the reliability of power supply.
[1] | 洪梅子, 吴迪, 李鹏, 黎恒烜, 文博, 雷杨, 杜镇安. 2017年湖北电网10kV-110kV继电保护及安全自动装置设备运行情况分析[J]. 湖北电力, 2018, 42(1): 1-5. |
[2] | 唐赓. 380V低压回路“越级跳闸”问题的研究[J]. 自动化技术与应用, 2017, 36(8): 81-84. |
[3] | 曹留柱, 曲德臣, 李民中, 王辉. 电力监控系统防越级跳闸方案的研究[J]. 工矿自动化, 2011, 37(8): 179-182. |
[4] | 黄振喜, 徐光彬, 周秋鹏. 变电站建筑装配式建设方案探讨[J]. 湖北电力, 2017, 41(1): 47-50. |
[5] | 宋鹏飞, 冯庆冬. 核电站低压厂用变压器零序保护的分析与改进[J]. 核科学与工程, 2016, 36(2): 245-250. |
[6] | 齐波. 中性点经高阻接地方式下配电网零序电流测量的研究[D]: [硕士学位论文]. 北京: 华北电力大学, 2006. |
[7] | 李婷. 系统运行方式对零序保护的影响分析[D]: [硕士学位论文]. 天津: 天津大学, 2012. |
[8] | 李文俊, 程志伟, 薛忠新, 孟海强. 基于光纤通信的防越级跳闸方案设计和应用[J]. 电力系统保护与控制, 2015, 43(21): 131-135. |
[9] | 李文江, 宋莉, 张文超, 范燕萍. 基于光纤数字通信的煤矿供电防越级跳闸保护设备应用研究[J]. 电子技术应用, 2011, 37(4): 26-28. |
[10] | Degeneff, R.C., Gutierrez, M.R. and Mckenny, P.J. (1992) A Method for Constructing Reduced Order Transformer Models for System Studies from Detailed Lumped Parameter Models. IEEE Transactions on Power Delivery, 7, 649-655. https://doi.org/10.1109/61.127062 |
[11] | Hao, W.U. (2008) Main Protection Con-figuration and Setting for Step-Down Substation Transformers of the Mechanical Plant. Journal of Sichuan University of Science & Engineering (Natural Science Edition), 21, 95-96. |
[12] | 叶锦娇. 煤矿井下电网防越级跳闸技术研究[J]. 煤矿机械, 2017, 38(1): 12-14. |
[13] | 崔智明. 煤矿井下供电越级跳闸问题的解决方案[J]. 煤矿机电, 2011(5): 56-57. |
[14] | 米春荣, 朱俊彦, 贾东立. DMP5000供电数字化防越级跳闸保护系统的应用研究[J]. 机械管理开发, 2013(3): 6-7. |
[15] | 李忠奎. 煤矿井下电网越级跳闸故障识别及防治技术研究[J]. 煤矿现代化, 2017(4): 100-102. |
[16] | 郭志安. 东曲矿电力系统防越级试验及应用[J]. 电子制作, 2012(9): 25-26. |
[17] | Nong, D.F. and Tao, L. (2009) Optimization of Protection Configuration for 10kV Station Transformers of Longtan Hydropower Station. Power System Technology, 33, 216-221. |
[18] | 雷杨, 杜镇安, 张侃君, 洪梅子. 关于变电站远方操作技术的分析[J]. 湖北电力, 2016, 40(1): 15-18. |
[19] | 潘广林. 关于低压厂用变压器出现越级跳闸分析及解决方法[J]. 数字技术与应用, 2011(3): 134-135. |
[20] | 何仰赞, 温增银. 电力系统分析下[M]. 武汉: 华中科技大学出版社, 2016. |
[21] | 张保会, 尹项根. 电力系统继电保护[M]. 第2版. 北京: 中国电力出版社, 2010. |
[22] | 陈军生. 配电室进线越级跳闸问题的解决[J]. 电力设备管理, 2018(2): 41-42. |
[23] | 江荣有. 降低变电站越级跳闸故障的攻关实践[J]. 铜业工程, 2015(6): 61-65. |
[24] | 杨友. 低压断路器级间配合分析[J]. 中国新技术新产品, 2016(15): 64-66. |
[25] | 孟宪章. 低压断路器[M]. 北京: 中国电力出版社, 2006. |