全部 标题 作者
关键词 摘要

OALib Journal期刊
ISSN: 2333-9721
费用:99美元

查看量下载量

相关文章

更多...

Optimal Operation Strategies for a Large Multi-Chiller System Based on Cooling Load Forecast

DOI: 10.4236/jsea.2019.1212033, PP. 540-561

Keywords: Large Multi-Chiller System, Operation Strategies, Cooling Load Forecast, Energy Saving, Optimal Design

Full-Text   Cite this paper   Add to My Lib

Abstract:

In semiconductor and electronics factories, large multi-chiller systems are needed to satisfy strict cooling load requirements. In order to save energy, it is worthwhile to design the chilled water system operation. In this paper, an optimal flexible operation scheme is developed based on a two-dimensional time-series model to forecast the cooling load of multi-chiller systems with chiller units of different cooling capacities running in parallel. The optimal integrity scheme can be obtained using the Mixed Integer Nonlinear Programming method, which minimizes the energy consumption of the system within a future time period. In order to better adapt the change of cooling load, the operation strategy of regulating the chilled water flowrates is employed. The chilled water flowrates are set as a design variable. When the chillers are running, their chilled water flowrates can vary within limits, whereas the flowrates are zero when the chillers are unloaded. This forecasting method provides integral optimization within a future time period and offers the operating reference for operators. The power and advantages of the proposed method are presented using an industrial case to help readers delve into this matter.

References

[1]  Hodge, B.K. and Taylor, R.P. (1999) Analysis and Design of Energy Systems. Prentice Hall, Upper Saddle River, NJ.
[2]  Lu, L., Cai, W., Chai, Y. and Xie, L. (2005) Global Optimization for Overall HVAC Systems Part I Problem Formulation and Analysis. Energy Conversion and Management, 46, 999-1014.
https://doi.org/10.1016/j.enconman.2004.06.012
[3]  Wang, S.W. and Ma, Z.J. (2008) Supervisory and Optimal Control of Building HVAC Systems: A Review. HVAC & R Research, 14, 3-32.
https://doi.org/10.1080/10789669.2008.10390991
[4]  ASHRAE (2007) ASHRAE Handbook—HVAC Applications (SI), Supervisory Control Strategies and Optimization, Chapter 41. American Society of Heating, Refrigerating and Air-Conditioning Engineers Inc., Atlanta, GA.
[5]  Gordon, J.M., Ng, K.C. and Chua, H.T. (1995) Centrifugal Chillers: Thermodynamic Modelling and a Diagnostic Case Study. International Journal of Refrigeration, 18, 253-257.
https://doi.org/10.1016/0140-7007(95)96863-2
[6]  Gordon, J.M., Ng, K.C., Chu, H.T. and Lim, C.K. (2000) How Varying Condenser Coolant Flow Rate Affects Chiller Performance: Thermodynamic Modeling and Experimental Confirmation. Applied Thermal Engineering, 20, 1149-1159.
https://doi.org/10.1016/S1359-4311(99)00082-4
[7]  Yao, Y., Lian, Z.W. and Hou, Z.J. (2004) Optimal Operation of a Large Cooling System Based on an Empirical Model. Applied Thermal Engineering, 24, 2303-2321.
https://doi.org/10.1016/j.applthermaleng.2004.03.006
[8]  Chang, Y.C. (2004) A Novel Energy Conservation Method—Optimal Chiller Loading. Electric Power Systems Research, 69, 221-226.
https://doi.org/10.1016/j.epsr.2003.10.012
[9]  Braun, J.E. and Diderrich, G.T. (1990) Near-Optimal Control of Cooling Towers for Chilled-Water Systems. ASHRAE Transactions, 96, 806-813.
[10]  Chan, K.L., Lee, W.M. and Yuen, K.K. (2011) An Integrated Model for the Design of Air-Cooled Chiller Plants for Commercial Buildings. Building and Environment, 46, 196-209.
https://doi.org/10.1016/j.buildenv.2010.07.013
[11]  Surapong, C., Liu, B., Nguyen, H.Q. and Tian, W. (1996) Improving Air-Conditioning and Saving Electricity in the Spinning Industry. Energy Sources, 18, 627-635.
https://doi.org/10.1080/00908319608908795
[12]  Lu, L., Cai, W., Chai, Y. and Xie, L. (2005) Global Optimization for Overall HVAC systems—Part II Problem Solution and Simulations. Energy Conversion and Management, 46, 1015-1028.
[13]  Yu, F.W. and Chan, K.T. (2008) Optimization of Water-Cooled Chiller System with Load-Based Speed Control. Applied Energy, 85, 931-950.
https://doi.org/10.1016/j.apenergy.2008.02.008
[14]  Braun, J.E. (1988) Methodologies for the Design and Control of Chilled Water Systems. Ph.D. Thesis, University of Wisconsin-Madison, Madison, WI.
[15]  Ponce-Ortega, J.M., Serna-González, M. and Jiménez-Gutiérrez, A. (2007) MINLP Synthesis of Optimal Cooling Networks. Chemical Engineering Science, 62, 5728-5735.
https://doi.org/10.1016/j.ces.2007.05.014
[16]  Soliman, S.A., Persaud, S. and El-Nager, K. (1997) Application of Least Absolute Value Parameter Estimation Based on Linear Programming to Short-Term Load Forecasting. International Journal of Electrical Power & Energy Systems, 19, 209-216.
https://doi.org/10.1016/S0142-0615(96)00048-8
[17]  Yao, Y., Lian, Z.W., Liu, S.Q. and Hou, Z.J. (2004) Hourly Cooling Load Prediction by a Combined Forecasting Model. International Journal of Thermal Sciences, 43, 1107-1118.
https://doi.org/10.1016/j.ijthermalsci.2004.02.009
[18]  Hahn, H., Meyer-Nieberg, S. and Pickl, S. (2009) Electric Load Forecasting Methods: Tools for Decision Making. European Journal of Operational Research, 199, 902-907.
https://doi.org/10.1016/j.ejor.2009.01.062

Full-Text

Contact Us

service@oalib.com

QQ:3279437679