全部 标题 作者
关键词 摘要

OALib Journal期刊
ISSN: 2333-9721
费用:99美元

查看量下载量

相关文章

更多...

A Study on Unified Testing Method for IEC 61850 Based Server with Focus on Setting Group Function

DOI: 10.4236/sgre.2018.910012, PP. 186-198

Keywords: IEC 61850, Substation Automation, IED, Function Test, Setting Group, Conformance Testing, Electrical Testing, Unified Testing, UCAIUG

Full-Text   Cite this paper   Add to My Lib

Abstract:

The digital substation system consists of an Intelligent Electronic Device (IED) which requires information for the supervision, protection, and control, as well as a client operating system for substation operation. IEC 61850 communication standard has been defined for information exchange between heterogeneous digital devices in such substations. Currently, the Korea Electric Power Corporation (KEPCO) digital substation system uses unbuffered reporting and Generic Object Oriented Substation Events (GOOSE) communication functions for monitoring, protection and control automation. However, it is expected that the Setting Group function will be needed to operate adaptive intelligent substation system. The Setting Group function is advantageous in that it is possible to change the setting of the IED in one unified way through the client operating system, rather than changing the correction value of an IED through different manufacturer-based engineering tools. In order to utilize the Setting Group function of the IED in real substation scenario, it is necessary to test both the communication function with the host operating device and the electric functional test to ensure that correction value is properly changed. In this paper, we introduce the IEC 61850 Setting Group function, and propose a method that can integrate communication function and electrical function test of an IED conforming to the setting group functionality. We also tested the Setting Group function of the actual IED device through the proposed integrated functional test method and analyzed the results. We were able to simplify the process of testing both the electrical and communication signals in digital substations.

References

[1]  Brunner, C. (2008) The Impact of IEC 61850 on Protection. Proceedings of the IET 9th International Conference on Developments in Power System Protection (DPSP 2008), Glasgow, 17-20 March 2008, 14-19.
https://doi.org/10.1049/cp:20080003
[2]  Horalek, J., Matyska, J. and Sobeslav, V. (2013) Communication Protocols in Substation Automation and IEC 61850 Based Proposal. Proceedings of the IEEE 14th International Symposium on Computational Intelligence and Informatics (CINTI), Budapest, 19-21 November 2013, 321-326.
https://doi.org/10.1109/CINTI.2013.6705214
[3]  Huang, W. (2018) Learn IEC 61850 Configuration in 30 Minutes. Proceedings of the 71st Annual Conference for Protective Relay Engineers (CPRE), College Station, TX, 26-29 March 2018, 1-5.
https://doi.org/10.1109/CPRE.2018.8349803
[4]  Gupta, R.P. (2008) Substation Automation Using IEC61850 Standard. Proceedings of the 15th National Power Systems Conference (NPSC), IIT Bombay, Mumbai, 16-18 December 2008.
http://www.krec.ir/Automation/Substation_Automation_Using_IEC61850_Standard.pdf
[5]  Roostaee, S., Hooshmand, R. and Ataei, M. (2011) Substation Automation System Using IEC 61850. Proceedings of the 5th International Power Engineering and Optimization Conference, Shah Alam, Selangor, 6-7 June 2011, 393-397.
https://doi.org/10.1109/PEOCO.2011.5970443
[6]  Khavnekar, A., Wagh, S. and More, A. (2015) Comparative Analysis of IEC 61850 Edition-I and II Standards for Substation Automation. Proceedings of the IEEE International Conference on Computational Intelligence and Computing Research (ICCIC), Madurai, 10-12 December 2015, 1-6.
https://doi.org/10.1109/ICCIC.2015.7435756
[7]  Apostolov, A. (2017) Impact of IEC 61850 Edition 2 on the Object Modelling of Distribution Protection IEDs. CIRED—Open Access Proceedings Journal, 2017, 1184-1187.
https://doi.org/10.1049/oap-cired.2017.0495
[8]  Schossig, T. (2018) Application of Settings and Setting Groups in IEC 61850. The Journal of Engineering, 2018, 967-970.
https://doi.org/10.1049/joe.2018.0191
[9]  Lee, N.H., Jang, B.T. and Song, I.J. (2009) The Testing Method of Data Transmission Services of IEC 61850 Based Client. Proceedings of the Transmission & Distribution Conference & Exposition: Asia and Pacific, Seoul, 26-30 November 2009, 1-4.
https://doi.org/10.1109/TD-ASIA.2009.5356912
[10]  Choi, C., Park, J., Han, J., Shin, Y., Kim, Y. and Shim, E. (2011) The Development of a Client Conformance Tool Based on IEC 61850. Proceedings of the International Conference on Electrical Machines and Systems, Beijing, 20-23 August 2011, 1-5.
https://doi.org/10.1109/ICEMS.2011.6073718
[11]  Muschlitz, B. (2006) IEC 61850 Conformance Testing: Goals, Issues and Status EnerNex Corporation. Presented at DistribuTECH 2006, Tampa, Florida Feb. 7-9 2016.
http://romvchvlcomm.pbworks.com/f/Muschlitz61850conftest.pdf
[12]  Udren, E.A., Strabbing, W. and Dolezilek, D. (2007) \"IEC 61850: Role of Conformance testing in Successful Integration. Proceedings of the 19th International Conference and Exhibition on Electricity Distribution, Vienna, 21-24 May 2007.
[13]  (2013) Communication Networks and Systems for Power Utility Automation Part 7-1: Basic Communication Structure Principles and Models, IEC 61850 Standard, 2013.
[14]  (2013) Communication Networks and Systems for Power Utility Automation Part 7-2: Basic Communication Structure—Abstract Communication Service Interface (ACSI), IEC 61850 Standard, 2013.
[15]  Schimmel, R. (2013) Conformance Test Procedures for Server Devices with IEC 61850-8-1 Edition 2 Interface-Revision 1.