大型电力变压器火灾安全研究

DOI: 10.13336/j.1003-6520.hve.2015.10.026, PP. 3378-3384

Keywords: 变压器,火灾安全,电弧,压力容器,套管,油箱,预防措施,统计

Full-Text   Cite this paper   Add to My Lib

Abstract:

为总结变压器火灾相关经验,结合国际大电网会议(CIGRE)变压器(A2)工作组所开展的研究以及中国电力科学研究院的统计情况,通过对变压器火灾时内部包括电弧能量、气体产生、压强计算模型、压力容器和压力释放等方面,对其内部电弧和油箱破裂进行了分析,并给出了国外和国内的变压器火灾概率的相关统计国外变压器火灾发生概率为(0.04%~0.25%)/a,根据中国电力科学研究院近20a收集的事故统计,国内变压器火灾发生概率约为(0.01%~0.03%)/a。套管故障是导致变压器起火的重要原因之一,通过模拟分析了故障发生过程;在此基础之上,结合运行经验,从不同角度全面地给出了降低变压器火灾风险的措施。

References

[1]  Jonsson L. Fire and safety aspects on high voltage condenser bushings[C]∥CIGRE, Transformer Technology Conference. Sydney, Australia: CIGRE, 2008.
[2]  Petersen A, Austin P L. Impact of recent transformer failures and fires-australian and new zealand experiences[C]∥CIGRÉ A2 Colloquium. Moscow, Russia: CIGRE, 2005.
[3]  Foata M. Power transformer fire risk assessment[C]∥CIGRE, Transformer Technology Conference. Sydney, Australia: CIGRE, 2008.
[4]  Kawamura T, Ueda M, Ando K, et al . Prevention of tank rupture due to internal fault of oil filled transformers[C]∥CIGRE. Paris, France: CIGRE, 1988.
[5]  Dastous J B, Lanteigne J, Foata M. Numerical method for the investigation of fault containment and tank rupture of power transformers[J]. IEEE Transactions on Power and Energy Society, 2009, 25(1): 1657-1665.
[6]  Lee J Y, Ham J K, Yang J C, et al . Tank rupture prevention technology for a large power transformer[C]∥CIGRÉ. Paris, France: CIGRE, 2010.
[7]  Ringlee R J, Roberts N W. Tank pressures resulting from internal explosions[J]. Transactions of the American Institute of Electrical Engineers, 1960, 78(4): 1705-1710.
[8]  Kawamura T. Prevention of tank rupture due to internal fault of oil-filled transformer[C]∥CIGRÉ. Paris, France: CIGRE, 1988.
[9]  Trencham H. Circuit breaking[M]. London, UK: Butterworth Scientific Publications, 1953.
[10]  Castonguay J, Théorêt A. Comportement chimique de l'huile minérale Voltesso 35 dansles disjoncteurs-réenclencheurs McGraw-Edison type CWVE 24.9 kV, 560 Ampères[R]. [S.l.]: Hydro-Québec IREQ Internal Report 1138C, 1975.
[11]  Goto K, Miura Y. The pressure rise during the internal fault in oil-filled transformer[C]∥CIGRÉ SC12 Colloquium. Paris, France: CIGRE, 1987.
[12]  Cuk N P. Oil tank explosion resistance[R]. Canada: Canadian Electricity Association, 1990.
[13]  Darian L A, Efremov V P, Kozlov A V, et al . The gas formation in the transformer oil under action of electrical arc and partial discharges[C]∥CIGRÉ International Colloquium on Transformer Research and Asset Management. Croatia: CIGRE, 2009.
[14]  Barkan P, Damsky B P, Ettlinger L F, et al . Overpressure phenomena in distribution transformers with low impedance faults: experiment and theory[J]. IEEE Transactions on Power Apparatus and Systems, 1976, 95(1): 37-48.
[15]  Carrander K, Häggblad B. Simulation of mechanical stresses in transformer tanks due to explosions caused by electrical arcs[C]∥CIGRE, Transformer Technology Conference. Sydney, Australia: CIGRE, 2008.
[16]  Working Group A2.33. Guide for transformer fire safety practices[R]. Paris, France: CIGRE, 2013.

Full-Text

Contact Us

service@oalib.com

QQ:3279437679

WhatsApp +8615387084133