不同波形参数冲击电压下油-隔板绝缘放电特性

DOI: 10.13336/j.1003-6520.hve.2015.06.028, PP. 1974-1980

Keywords: 特快速暂态过电压,油纸绝缘,击穿特性,振荡频率,波前时间,放电痕迹

Full-Text   Cite this paper   Add to My Lib

Abstract:

变电站布置、绕组内部谐振等因素会使得侵入变压器内部的雷电过电压的波形参数异于标准波形;此外,GIS中隔离开关操作造成的特快速暂态过电压(VFTO)带来的危害也与日俱增。为此设计了一种油-隔板绝缘模型,研究了波前时间、振荡频率对击穿特性的影响,以及VFTO下油-隔板绝缘模型击穿特性和隔板几何位置对放电特性的影响。结果表明,油-隔板绝缘模型击穿电压随波前时间的减小而增高;振荡频率增大会提高模型击穿电压,最高提高达30%;油-隔板绝缘模型在VFTO下的击穿电压较标准雷电冲击电压下提高10%;单层隔板时模型击穿电压随纸板与球电极之间距离的增大逐渐降低。

References

[1]  程养春,刁常晋,刘少宇,等. 恒定电压下油纸绝缘局部放电发展规律及缺陷状态诊断[J]. 高电压技术,2013,39(5):1061-1068. CHEN Yangchun, DIAO Changjin, LIU Shaoyu, et al . Developing laws and severity diagnosis of partial discharge defects on oil-paper insulation[J]. High Voltage Engineering, 2013, 39(5): 1061-1068.
[2]  Kolb J F, Joshi R P, Xiao S, et al . Streamers in water and other dielectric liquids[J]. Journal of Physics D: Applied Physics, 2008, 41(23): 234007.
[3]  Liu R, Jaksts A. Breakdown processes in transformer insulation under LI voltages[C]∥2005 IEEE International Conference on Dielectric Liquids. Vasteras, Sweden: IEEE, 2005.
[4]  Fujita S, hosokawa N, Shibuya Y. Experimental investigation of high frequency voltage oscillation in transformer windings[J]. IEEE Transaction on Power Delivery, 1998, 13(4): 1021-1027.
[5]  Massala G, Lesaint O. A comparion of negative and positive streamers in mineral oil in large gaps[J]. Journal of Physics D: Applied Physics, 2001, 34(10): 1525.
[6]  Nakanishi K, Fujita S, Kurita H. et al . High frequency voltage oscillation in transformer windings and electrical breakdown properties of interturn insulation immersed in oil at VFT voltage[C]∥Annual Report Conference on Electrical Insulation and Dielectric Phenomena. Minneapolis, USA: IEEE, 1997.
[7]  Venkatesan S, Usa S. Impulse strength of transformer insulation with nonstandard waveshapes[J]. IEEE Transactions on Power Delivery, 2007, 22(4): 2214-2221.
[8]  Usa S, Udayakumar K, Jayashankar V. Modified disruptive effect method as a measure of insulation strength for non-standard lighting waveforms[J]. IEEE Transactions on Power Delivery, 2002, 17(2):510-515.
[9]  Garnacho F, Perez J, Aro M, et al . Evaluation procedures for lightning impulse parameters in case of waveforms with oscillations and/or an overshoot[J]. IEEE Transaction on Power Delivery, 1997, 12(2):640-649.
[10]  Wang Z, Zhang Q, Wang T, et al . The oil-paper insulation breakdown characteristics under non-standard lightning impulse voltages[C]∥Conference on Electrical Insulation and Dielectric Phenomena. Shenzhen, China: IEEE, 2013: 883-886.
[11]  Viswanatha C, Jsundara Rajan, Nema R.S, et al . Study of anomalous breakdown of paper-oil insulation under unconventional voltages[C]∥International Conference on Dielectric Liquids. Nara, Japan: IEEE, 1999.
[12]  王梦云. 2004年度110 kV及以上变压器事故统计分析[J]. 电力设备,2005,6(11):31-38. WANG Mengyun. Statistics and analysis of 110 kV and the above transformer fault in 2004[J]. Electrical Equipment, 2005, 6(11): 31-38.
[13]  Vandermaar A J, Wang M, Neilson J B, et al . The electrical breakdown characteristics of oil-paper insulation under steep front impulse voltages[J]. IEEE Transactions on Power Delivery, 1994, 9(4): 1926-1935.
[14]  Naidu S R, Neilson J B, Srivastava K D. The volt-time characteristics of oil-impregnated paper insulation in the submicrosecond and microsecond regime[J]. IEEE Transactions on Electrical Insulation, 1989 , 24(1): 39-46.
[15]  Okabe S. Evaluation of breakdown characteristics of oil-immersed transformers under non-standard lightning impulse waveforms - definition of non-standard lightning impulse waveforms and insulation characteristics for waveforms including pulses[J]. IEEE Transactions on Dielectrics and Electrical Insulation, 2007, 14(1): 146-155.
[16]  Okabe S. Evaluation of breakdown characteristics of oil-immersed transformers under non-standard lightning impulse waveforms - insulation characteristics for non-standard lightning impulse waveforms with oscillations[J]. IEEE Transactions on Dielectrics and Electrical Insulation, 2007, 14(3): 679-688.
[17]  Okabe S, Takami J. Evaluation of breakdown characteristics of oil-immersed transformers under non-standard lightning impulse waveforms - method for converting non-standard lightning impulse waveforms into standard lightning impulse waveforms[J]. IEEE Transactions on Dielectrics and Electrical Insulation, 2008, 15(5): 1288-1296.
[18]  Ikeda M, Fukumoto S, Takao H. Breakdown characteristics of oil and paper insulation for a very fast transient voltage[J]. Electrical Engineering in Japan, 2002,141(4): 16-24.
[19]  Pfeffer A, Tenbohlen S. Evaluation of parameters of lightning impulse voltages from transformer tests using the new k-factor approach[J]. IEEE Transactions on Dielectrics and Electrical Insulation, 2010,17(3): 947-952.
[20]  胡 伟,许佐明,张施令,等. 雷电冲击试验中特高压油纸电容式套管末屏电位升高原因分析[J]. 高电压技术,2013,39(3):577-583. HU Wei, XU Zuoming, ZHANG Shiling, et al . Analysis on potential rise on UHV oil-paper capacitor bushing’s end shield under lightning imupulse test[J]. High Voltage Engineering, 2013, 39(3): 577-583.
[21]  陈维江,曾 嵘,贺恒鑫. 长空气间隙研究进展[J]. 高电压技术,2013,39(6):1281-1295. CHEN Weijiang, ZENG Rong, HE Hengxin, et al . Rearch progress of long air gap discharges[J]. High Voltage Engineering, 2013, 39(6): 1281-1295.
[22]  沙彦超,周远翔,孙清华,等. 直流电压分量对交直流叠加电压下油纸绝缘沿面闪络的影响[J]. 高电压技术,2013,39(6):1337-1343. SHA Yanchao, ZHOU Yuanxiang, SUN Qinghua, et al . Influence of DC voltage on creepage flashover of oil-paper insulation under composite AC and DC voltage[J]. High Voltage Engineering, 2013, 39(6): 1337-1343.
[23]  Sathish J, Kumar S, Usa S, et al . Effective model for prediction of impulse strength of oil-impregnated paper insulation under non-standard impulse voltages[C]∥International Conference on Power System Technology. Singapore: IEEE, 2004.