全部 标题 作者
关键词 摘要

OALib Journal期刊
ISSN: 2333-9721
费用:99美元

查看量下载量

相关文章

更多...
电网技术  2012 

应用矩量法的变电站内工频电磁场计算及实测

, PP. 189-194

Keywords: 变电站,矩量法,电磁环境,工频电场,工频磁感应强度,限值

Full-Text   Cite this paper   Add to My Lib

Abstract:

本文首先着重介绍了矩量法(MOM)的计算原理,推导相应的计算公式,然后利用该方法对佛山市110kV桂城变电站110kV配电区的电磁环境进行了相应的计算,并于现场实测进行了对比,结果表明,该方法能够精确计算变电站内电磁场。接着给出了佛山其他110kV—500kV变电站现场测量数据,有的变电站内部分区域的工频电场强度和磁感应强度超过其限值。为此,分析了变电站内架空线路高度、间距、线径和大地电阻率对电磁场分布的影响,以供相关人士参考。

References

[1]  Harrington R F.Field computation by moment methods[M].New York,Macmillan,1968.
[2]  Selby A,Dawalibi F.Determination of current distribution in energized conductors for the computation of electromagnetic fields[J].IEEE Trans on Power Delivery,1994,9(2):1069-1078.
[3]  HJ/T 24—1998,500 kV超高压送变电工程电磁辐射环境影响评价技术规范[S].
[4]  杨勇,陆家榆,鞠勇.交流线路与?800 kV直流线路同走廊时的地面混合电场研究[J].电网技术,2009,33(15):54-59.
[5]  Yang Yong,Lu Jiayu,Ju Yong.Study on the hybrid electric field over the ground surface under AC lines and ?800 kV DC lines in the same corridor[J].Power System Technology,2009,33(15):54-59(in Chinese).
[6]  Russell B D.Measurement and characterization of substation electromagnetic transients[R].Palo Alto,CA:EPRI,1983.
[7]  DL/T 988—2005,高压交流架空送电线路、变电站工频电场和磁场测量方法[S].
[8]  黄道春,阮江军,文武.特高压交流输电线路电磁环境研究[J].电网技术,2007,31(1):6-11.
[9]  Huang Daochun,Ruan Jiangjun,Wen Wu.Study on electromagnetic environment of UHV AC transmission lines[J].Power System Technology,2007,31(1):6-11(in Chinese).
[10]  EPRI.EPRI TR 102006:Electromagnetic transients in substations [R].Palo Alto,CA:EPRI,1993.
[11]  万保权,邬雄,张广洲,等.500 kV输变线路和变电站电磁环境参数测量研究[R].武汉:国网电力科学研究院,2005.
[12]  邵方殷.我国特高压输电线路的相导线布置和工频电磁环境[J].电网技术,2005,29(8):1-7.
[13]  Shao Fangyin.Phase conductor configuration and power frequency electromagnetic environment of UHV transmission line in China [J].Power System Technology,2005,29(8):1-7(in Chinese).
[14]  王小凤.CDEGS软件在电力系统中的应用[D].杭州:浙江大学,2007.
[15]  SES Technologies.CDEGS user manual[R].Montreal:SES Technologies,2005.
[16]  Friedlander G D.UHV:onward and upward[J].IEEE Spectrum,1977,14(2):56-65.
[17]  Clarimont B A,Johnson G B,Zaffanella L E,et al.The effects of HVAC-HVDC line separation in a hybrid corridor[J].IEEE Trans on Power Delivery,1989,4(2):1338-1350.
[18]  Vernon L C,Richard D S.Effect of bundle orientation on transmission line audible noise and radio noise[J].IEEE Trans on Power Delivery,1994,9(3):1538-1544.
[19]  Dawalibi F P,Donoso F.Integrated analysis software for grounding,EMF,and EMI[J].IEEE Computer Applicat Power,1993,6(2):19-24.

Full-Text

Contact Us

service@oalib.com

QQ:3279437679