电网技术  2006 

电位降法测量接地电阻时的电流极引线长度分析

, PP. 41-44

Keywords: 变电站,接地电阻测量,全球定位系统,电位降法,电流极引线,高电压绝缘技术

Full-Text   Cite this paper   Add to My Lib

Abstract:

讨论了电流极引线长度对变电站接地电阻测量误差的影响,分析得到了不同土壤结构所要求的电流极引线长度。采用反向法测量接地电阻时,测量得到的接地电阻比真实接地电阻要小,但可将反向法测量得到的接地电阻作为变电站接地电阻测量值的下限。采用全球定位系统(globalpositioningsystem,GPS)确定测量电极与接地网之间的距离后,能够根据电位降法比较准确地测量接地电阻。实际测量结果表明,如果电流极引线过短,可通过辅助分析的方法得到实际接地电阻的电压极补偿点位置。

References

[1]  张波,崔翔,赵志斌,等.大型变电站接地网的频域分析方法[J].中国电机工程学报,2002,22(9):59-63. Zhang Bo,Cui Xiang,Zhao Zhibin,et al.Analysis of grounding grids at large scale substation in frequency domain[J].Proceedings of the CSEE,2002,22(9):59-63.
[2]  鲁志伟,文习山,史艳玲,等.大型变电站接地网工频接地参数的数值计算[J].中国电机工程学报,2003,23(12):89-93. Lu Zhiwei,Wen Xishan,Shi Yanling,et al.Numerical calculation of large substation grounding grids in industry frequency [J].Proceedings of the CSEE,2003,23(12):89-93.
[3]  ANSI/IEEE Std 81-1991,IEEE guide for measurement of impedance and safety characteristics of large,extended or interconnected grounding system[S].
[4]  何金良,余绍峰,曾嵘,等.变电所附近地下构筑物对接地电阻测量的影响[J].高压电器,2004,40(1):1,2. He Jinliang,Yu Shaofeng,Zeng Rong,et al.Influence of neighboring underground metal objects on measurement of substation grounding resistance[J].High Voltage Apparatus,2004,40(1):1,2.
[5]  曾嵘,陈未远,何金良.变电所接地阻抗测量方法及测试信息分析[J].高电压技术,2004,30(2):20,21, 38. Zeng Rong,Chen Weiyuan,He Jinliang.Measurement method and tests data analysis of grounding impedance of substation[J].High Voltage Engineering,2004,30(2):21,21,38.
[6]  窦鑫,何金良,曾嵘,等.变电所接地阻抗的感性分量分析[J].高压电器,2004,40(4):245,246. Dou Xin,He Jinliang,Zeng Rong,et al.Analysis of conductive component of grounding impedance at substation[J].High Voltage Apparatus,2004,40(4):245,246.
[7]  黄锐锋,李琳,张波,等.变电站接地网接地电阻近距离测法与系统开发[J].高电压技术,2004,30(9):27-29. Huang Ruifeng,Li Lin,Zhang Bo,et al.Novel method for measuring the grounding resistance of the substation grid with short leads and the system development[J].High Voltage Engineering,2004,30(9):27-29.
[8]  曾嵘,何金良,高延庆,等.电极位置对垂直三层土壤结构中接地系统接地电阻测量结果的影响[J].清华大学学报(自然科学版),2001,41(3):28-31. Zeng Rong,He Jinliang,Gao Yanqing,et al.Effects of electrode placement on grounding resistance of grounding system measured in vertical three-layer soil[J].Journal of Tsinghua University (Science and Technology ),2001,41(3):28-31.
[9]  何金良,曾嵘,高延庆.电力系统接地技术研究进展[J].电力建设,2004,25(6):1-4. He Jinliang,Zeng Rong,Gao Yanqing.Progress of substation grounding technology of modern power system[J].Electric Power Construction,2004,25(6):1-4.
[10]  鞠勇,张波,崔翔,等.双层土壤中接地网接地电阻补偿测量法的修正曲线[J].电网技术,2003,27(1):44-46,51. Ju Yong,Zhang Bo,Cui Xiang,et al.Correction curve for grounding resistance value of ground mesh buried in two-layer soils measured by compensating method[J].Power System Technology,2003,27(1):44-46,51.
[11]  Zeng Rong,He Jinliang,Gao Yanqing,et al.Grounding resistance measurement analysis of grounding system in vertical-layered soil [J].IEEE Trans on Power Delivery,2004,19(4):1553- 1559.
[12]  Zeng Rong,He Jinliang,Tu Youping,et al.Influence of overhead transmission line on grounding impedance measurement of substation[J].IEEE Trans on Power Delivery,2005,20(2): 1226-1234.
[13]  张丽萍,袁建生,李中新.变电站接地网不等电位模型数值计算[J].中国电机工程学报,2000,20(1):1-3,69. Zhang Liping,Yuan Jiansheng,Li Zhongxin.Calculation of substation grounding grids with unequal-potential model [J].Proceedings of the CSEE,2000,20(1):1-3,69.
[14]  李中新,袁建生,张丽萍.变电站接地网模拟计算[J].中国电机工程学报,1999,19(5):76-79. Li Zhongxin,Yuan Jiansheng,Zhang Liping.Numerical calculation of substation grounding system[J].Proceedings of the CSEE,1999, 19(5):76-79.
[15]  陆家榆,庞廷智,薛辰东,等.城区变电站地电位模拟测试研究[J].电网技术,2004,28(14):57-61. Lu Jiayu,Pang Tingzhi,Xue Chendong,et al.Study on simulation test and measurement of ground potential of substation in city proper [J].Power System Technology,2004,28(14):57-61.
[16]  王坚强,彭岳林,杨文兵.垂直层状介质中接地网接地参数的计算[J].电网技术,1995,19(2):27-33. Wang Jianqiang,Peng Yuelin,Yang Wenbing.The parameter calculation of grounding nets in vertical medium demarcation [J].Power System Technology,1995,19(2):27-33.
[17]  曾嵘,何金良,高延庆,等.垂直分层土壤中测试电极布置对变电站接地电阻的测量值的影响[J].电网技术,2000,24(10):36-39. Zeng Rong,He Jinliang,Gao Yanqing,et al.Influence of arrangement of electrodes on grounding resistance measurement of substation in vertical-layered soil[J].Power System Technology, 2000,24(10):36-39.
[18]  何金良,康鹏,曾嵘,等.青藏铁路110kV输变电工程五道梁和沱沱河变电站的土壤结构模型分析[J].电网技术,2005,29(20):10-14. He Jinliang,Kang Peng,Zeng Rong,et al.Soil structural model analysis of Wudaoliang and Tuotuohe substation of 110kV power transmission engineering of Qinghai-Tibet railway[J].Power System Technology,2005,29(20):10-14.
[19]  许军,蓝磊,文习山,等.三峡电站模型地网接地电阻小比例模型试验研究[J].电网技术,2003,27(1):38-40. Xu Jun,Lan Lei,Wen Xishan,et al.Small scale model test for grounding resistance of grounding mesh model for Three Gorges hydroelectric power station[J].Power System Technology,2003, 27(1):38-40.
[20]  孙结中,刘力.运用等值复数镜像法求解复合分层土壤结构的格林函数[J].中国电机工程学报,2003,23(9):146-151. Sun Jiezhong,Liu Li.Derivation of green’s function by equivalent complex image method in a horizontal and vertical combined-layer soil structure[J].Proceedings of the CSEE,2003,23(9):146-151.
[21]  ANSI/IEEE Std 367-1987,IEEE recommended practice for determining the electric power station ground potential rise and induced voltage from a power fault[S].
[22]  GBT 17949.1-1999,接地系统的土壤电阻率、接地阻抗和地表电位测量导则[S].

Full-Text

Contact Us

service@oalib.com

QQ:3279437679

WhatsApp +8615387084133