为得出高海拔、低气压下污秽地区不同伞形结构复合绝缘子的爬电距离有效利用率,在大型多功能人工气候室内对高海拔、低气压条件下干弧距离比较接近的4组不同伞型结构的复合绝缘子及一张硅橡胶平板开展了污闪试验研究。根据真实复合绝缘子的污闪梯度与硅橡胶板的污闪梯度之比,可求得复合绝缘子的爬电距离有效利用率k。根据k及爬距与干弧距离之比(dCF系数),可计算得到电弧中间隙电弧的比例k1。分析了复合绝缘子污闪过程中k、k1的影响因素。结果表明,大小伞形dCF系数为3.55的复合绝缘子在海拔不超过2500m时爬电距离的利用率较高,当海拔升高到4000m时,大小伞形dCF系数为3.27的复合绝缘子具有较高的爬电距离有效利用率。爬电距离有效利用率与与盐密、气压均呈幂指数关系。

References

[1]  Kawamura T.Pressure dependence of DC breakdown of contaminated insulators[J].IEEE Trans on Dielectrics and Electrical Insulation,1982,EI-17(1):39-45.
[2]  Mercure H P.Insulator pollution performance at high altitude: major trends[J].IEEE Trans on Power Delivery,1989,4(2):1461-1468.
[3]  Jiang X L,Yuan J H,Zhang Z J,et al.Study on pollution flashover performance of short samples of composite insulators intended for ?800 kV UHV DC[J].IEEE Trans on Dielectrics and Electrical Insulation,2007,14(5):1192-1200.
[4]  Lan L,Gorur R S.Computation of AC wet flashover voltage of ceramic and composite insulators[J].IEEE Trans on Dielectrics and Electrical Insulation,2008,15(5):1346-1352.
[5]  蒋兴良,张志劲,胡建林,等.高海拔下不同伞形结构750 kV合成绝缘子短样交流污秽闪络特性及其比较[J].中国电机工程学报, 2005,25(12):159-164.
[6]  Jiang Xingliang,Zhang Zhijin,Hu Jianlin,et al.AC pollution flashover performance and comparison of short samples of 750 kV composite insulators with different configuration in high altitude area [J].Proceedings of the CSEE,2005,25(12):159-164(in Chinese).
[7]  李立浧,蒋兴良,孙才新,等.?800 kV 直流复合绝缘子短样人工污秽闪络特性研究[J].中国电机工程学报,2007,27(10):14-19.
[8]  Li Licheng,Jiang Xingliang,Sun Caixin,et al.Study on pollution flashover performance of short sample of ?800 kV UHV DC composite insulators[J].Proceedings of the CSEE,2007,27(10):14-19(in Chinese).
[9]  张福增,王黎明,关志成.复合绝缘子伞裙参数对直流污闪电压的影响[J].高电压技术,2010,36(3):603-608.
[10]  Zhang Fuzeng,Wang Liming,Guan Zhicheng.Influence of parameters for composite insulator on DC flashover voltage[J].High Voltage Engineering,2010,36(3):603-608(in Chinese).
[11]  Zhang F,Zhao J,Wang L,et al.Experimental investigation on outdoor insulation for DC transmission line at high altitudes[J].IEEE Trans on Power Delivery,2010,25(1):351-357.
[12]  张志劲.低气压下绝缘子(长)串污闪特性及直流放电模型研究[D].重庆:重庆大学,2006.
[13]  张志劲,蒋兴良,孙才新,等.低气压下绝缘子串直流污闪放电过程[J].电工技术学报,2009,24(4):30-35.
[14]  Zhang Zhijin,Jiang Xingliang,Sun Caixin,et al.DC pollution flashover process for insulator string at low air pressure [J].Transactions of China Electrotechnical Society,2009,24(4):30-35(in Chinese).
[15]  IEC 60507—1991,Artificial pollution tests on high-voltage insulators to be used on AC systems[S].
[16]  GB/T 4585—2004,交流系统用高压绝缘子的人工污秽试验[S].
[17]  袁前飞,舒立春,蒋兴良,等.低气压下不同伞型结构复合绝缘子交流污闪性能对比[J].高电压技术,2010,36(7):79-85.
[18]  Yuan Qianfei,Shu Lichun,Jiang Xingliang,et al.Comparison of AC pollution flashover performances for composite insulators with different configuration under low atmospheric pressure[J].High Voltage Engineering,2010,36(7):79-85(in Chinese).
[19]  田玉春,蒋兴良,舒立春,等.高海拔地区10 kV 合成绝缘子覆冰闪络特性和电压校正[J].高电压技术,2002,28(6):13-15.
[20]  Tian Yuchun,Jiang Xingliang,Shu Lichun,et al.AC flashover performance and voltage correction of iced 10 kV composite insulator in high altitude area[J].High Voltage Engineering,2002,28(6):13-15(in Chinese).
[21]  蒋兴良,舒立春,孙才新.电力系统污秽与覆冰绝缘[M].北京: 中国电力出版社,2009:71-74.
[22]  Liang X D,Wang S W,Fan J,et al.Development of composite insulators in China[J].IEEE Trans on Dielectrics and Electrical Insulation,1999,6(5):586-594.
[23]  Jiang X L,Yuan J H,Zhang Z J,et al.Study on AC pollution flashover performance of composite insulators at high altitude sites of 2800-4500 m[J].IEEE Trans on Dielectrics and Electrical Insulation, 2009,16(1):123-132.
[24]  Jiang X L,Yuan J H,Zhang Z J,et al.Study on AC artificial-contaminated flashover performance of various types of insulators[J].IEEE Trans on Power Delivery,2007,22(4): 2567-2574.
[25]  关志成.绝缘子及输变电设备外绝缘[M].北京:清华大学出版社, 2006:261-274.
[26]  Guan Z C,Zhang R Y.Calculation of DC and AC flashover voltage of polluted insulators[J].IEEE Trans on Dielectrics and Electrical Insulation,1990,25(4):723-729.
[27]  Ghosh P S,Chatteree N.Polluted insulator flashover mode1 for AC voltage[J].IEEE Trans on Dielectrics and Electrical Insulation,1995,2(1):128-136.
[28]  Rudakova V M,Tikhodeev N N.Influence of low air pressure on flashover voltage of polluted insulators:test data, generalization attempts and recommendations[J].IEEE Trans on Power Delivery, 1989,4(1):607-613.
[29]  Frywell J.Influence of high altitudes on the flashover voltage of insulators[J].Elteknik,1966,9(1):1-3.
[30]  Jiang X L,Yuan J H,Shu L C,et al.Comparison of DC pollution flashover performances of various types of porcelain,glass,and composite insulators[J].IEEE Trans on Power Delivery,2008,23(2):1183-1190.
[31]  刘泽洪.复合绝缘子使用现状及其在特高压输电线路中的应用前景[J].电网技术,2006,30(12):1-7.
[32]  Liu Zehong.Present situation and prospects of applying composite insulators to UHF transmission lines in China[J].Power System Technology,2006,30(12):1-7(in Chinese).
[33]  宿志一,范建斌.复合绝缘子用于高压及特高压直流输电线路的可靠性研究[J].电网技术,2006,30(12):16-23.
[34]  Su Zhiyi,Fan Jianbin.Research on reliability of composite insulators used in EHV and UHV transmission lines[J].Power System Technology,2006,30(12):16-23(in Chinese).
[35]  陈爱军.不同盐密和灰密对110 kV复合绝缘子污秽闪络特性的影响研究[D].重庆:重庆大学, 2006.

Full-Text

Contact Us

service@oalib.com

QQ:3279437679

WhatsApp +8615387084133