10 kV异步电动机定子绕组老化槽放电指纹分布规律的研究

, PP. 35-43

Keywords: 10kV异步电动机,定子绝缘,槽放电,放电指纹,绝缘老化

Full-Text   Cite this paper   Add to My Lib

Abstract:

在10kV异步电动机制造过程中,为抑制运行中定子槽内发生放电,常在绕组直线部分包绕一定阻值的半导电层。尽管如此,电动机在运行过程中,由于电磁力的作用,槽放电仍然是导致电动机定子绝缘故障的主要原因之一。针对这一问题,设计并制作了宽度可调单层绕组定子铁心槽部模型,研究了F级绝缘10kV异步电动机真机定子绕组绝缘在不同程度磨损老化后槽放电指纹的分布规律。通过提取表征放电特性的特征量,给出了定子绕组在不同磨损老化状态下,槽放电指纹随电压的变化规律,为10kV电动机绝缘在线监测和寿命评估提供了判断依据。

References

[1]  IEC Standard 60505―2011 Evaluation and qualification of electrical insulation systems[S].2011.
[2]  STONE G C,BOULTER E A,CULBERT I,et al.Electrical insulation for rotating machines[M]. Piscataway, NJ: IEEE Press, 2004.
[3]  STONE G C,WU R.Examples of stator winding insulation deterioration in new generators[C]//Proceedings of the 9th International Conference on Properties and Applications of Dielectric Materials.[S.l.]:IEEE,2009:180-185.
[4]  JACKSON R J,WILSON A.Slot-discharge activity in air-cooled motors and generators[J]. IEE Proceedings B:Electric Power Applications, 1982,129(3):159-167.
[5]  R??DIGER S, LAIRD T,WATTERS C.Case study using an additional neutral point PD sensor for generator stator monitoring[C]//IEEE International Symposium on Electrical Insulation.[S.l.]:IEEE,2008:213-219.
[6]  HUDON C,B??LEC M.Partial discharge signal interpretation for generator diagnostics[J]. IEEE Transactions on Dielectrics and Electrical Insulation,2005,12(2):297-319.
[7]  L??VESQUE M, HUDON C, B??LEC M,et al.Measurements of slot partial discharges with an antenna during accelerated aging[C]//2009 IEEE Electrical Insulation Conference.[S.l.]:IEEE,2009:458-462.
[8]  HUDON C,CHAABAN M,BELEC M,et al.Effect of temperature and thermal expansion on slot PD activity[C]//Electrical Insulation Conference and Electrical Manufacturing Expo..Nashville, TN: IEEE,2007:122-126.
[9]  LEVESQUE M, DAVID ??,HUDON C,et al.Effect of surface degradation on slot partial discharge activity[J]. IEEE Transactions on Dielectrics and Electrical Insulation,2010,17(5):1428-1440.
[10]  STONE G C.Relevance of phase resolved PD analysis to insulation diagnosis in industrial equipment[C]//2010 International Conference on Solid Dielectrics.Potsdam, Germany:IEEE,2010:1-5.
[11]  STONE G C,MAUGHAN C V,NELSON D,et al.Impact of slot discharges and vibration sparking on stator winding life in large generators[J]. IEEE Electrical Insulation Magazine,2008,24(5):14-21.
[12]  STONE G C.A suggested approach for specifying PD testing as a new winding acceptance test[C]//Proc. IEEE Electrical Insulation Conference.[S.l.]:IEEE,2005:159-162.
[13]  宋建成.大电机主绝缘多因子老化特征参量的研究[D].西安:西安交通大学,1999.
[14]  尤鸿?,孟永鹏,成永红.大电机表面震动火花发展规律的研究[C]//2010电工测试技术学术交流会论文集.武汉:[s.n.],2010:193-197.
[15]  HUDON C,B??LEC M.Study of slot partial discharges in air-cooled generators[J]. IEEE Transactions on Dielectrics and Electrical Insulation,2008,15(6):1675-1690.