高压电器  2015 

高压开关柜无线测温系统设计及可靠性研究

, PP. 152-160

Keywords: 高压开关柜,ZigBee,环境,过热,电磁骚扰

Full-Text   Cite this paper   Add to My Lib

Abstract:

过热是影响高压开关柜测温系统供电稳定性的重要危害源,而开关柜内的电磁骚扰是影响测温系统工作稳定性的主要因素。文中研制了一种高压开光柜无线测温系统,用于提高设备运行可靠性。笔者分析了ZigBee测温系统工作原理,优化设计了温度采集器硬件、ZigBee模块和数据集中器硬件结构;探索获得了温度采集和通信的流程,并编制了相关软件。通过有限元热场仿真获得了温度采集器附近的热场分布情况,采用热隔离结构设计,降低了电池和采集器硬件模块的温度,消除了高温可能造成的测量系统爆炸隐患。通过修改工作流程增加握手协议,并增设放电二极管,提高了系统抗干扰性能,试验表明该系统可通过严格的电磁兼容试验。

References

[1]  巩宪锋,衣红钢,王长松,等.高压开关柜隔离触头温度监测研究[J]. 中国电机工程学报,2006,26(1):155-158. GONG Xianfeng, YI Honggang, WANG Changsong, et al. Research on temperature monitoring of isolators in HV switchgear[J]. Proceedings of the Chinese Society for Electrical Engineering,2006,26(1): 155-158.
[2]  HONG L,CAO C,LIU Q. Real-time temperature monitoring system for high voltage switchgear based on infrared wireless transmission[C]//2010 2nd International Conference on Information Science and Engineering(ICISE). Hangzhou,China: IEEE,2010: 2265-2268.
[3]  LI Y,CHENG W.A novel temperature monitoring system based on FBG for switchgear[C]//Asia-Pacific Power and Energy Engineering Conference(APPEEC). Chengdu,China: IEEE,2010: 1-4.
[4]  杨 武,王小华,荣命哲,等.基于红外测温技术的高压电力设备温度在线监测传感器的研究[J]. 中国电机工程学报,2002,22(9):113-117. YANG Wu,WANG Xiaohua,RONG Mingzhe,et al. On-line temperature measurements with infrared technology on high voltage device[J]. Proceedings of the Chinese Society for Electrical Engineering,2002,22(9): 113-117.
[5]  张 艳,田 竞,叶逢春,等.基于红外传感器的高压开关柜温度实时监测网络的研制[J]. 高压电器,2005,41(2):91-94. ZHANG Yan,TIAN Jing,YE Fengchun,et al. Development of temperature real-time monitoring network for high voltage switch cabinet based on IR sensor[J]. High Voltage Apparatus,2005,41(2): 91-94.
[6]  时 斌.光纤传感器在高压设备在线测温系统中的应用[J]. 高电压技术,2007,33(8):169-173. SHI Bin. HV switchgear temperature on-line monitoring system with distributed optical fiber sensor[J]. High Voltage Engineering,2007,33(8): 169-173.
[7]  邬 钢,李 进.光纤在开关柜触头温度监测中的应用[J]. 高电压技术,2006,32(2):122-122. WU Gang,LI Jin. Application of optical fiber in temperature monitoring of the contacts of switch cabinet[J]. High Voltage Engineering,2006,32(2): 122-122.
[8]  杨 帆.高压开关柜无线测温系统的研究[D]. 武汉:华中科技大学,2011. YANG Fan. The research of wireless temperature measurment system for the high-voltage switchgear[D]. Wuhan: Huazhong University of Science and Technology,2011.
[9]  HU Zhenfeng,GENG Xin,XIAO Jin,et al. Research and realization of on-line monitoring system for high voltage circuit breaker based on ZigBee technology[C]//2009 IEEE International Conference on Control and Automation. Christchurch,New Zealand: IEEE,2009: 190-195.
[10]  ZHANG J,DAI W,HUANG D,et al. ZigBee enabled remote temperature monitor system for high-voltage substations[C]//Spring World Congress on Engineering and Technology (S-CET). Xi’an,China:IEEE,2012: 1-4.
[11]  CAI B,JIN X,YAN S,et al. Application research on temperature WSN nodes in switchgear assemblies based on tinyos and ZigBee[C]//2011 4th International Conference on Electric Utility Deregulation and Restructuring and Power Technologies(DRPT). Weihai,China: IEEE,2011: 535-538.
[12]  吴光荣,章剑雄.基于ZigBee的高压开关柜无线温湿度监测系统[J]. 现代电子技术,2008,31(20):169-171. WU Guangrong,ZHANG Jianxiong. A kind of temperature and humidity monitoring system for high pressure switch cabinet based on ZigBee technology[J]. Modern Electronics Technique,2008,31(20): 169-171.
[13]  ZHANG G,LIU S. Study on electrical switching device junction temperature monitoring system based on Zigbee technology[C]//2010 International Conference on Computer Application and System Modeling(ICCASM). Taiyuan, China: IEEE,2010: 692-695.
[14]  周 岩,高 杨,刘婷婷,等.高压开关柜触头温度场的数值仿真分析[J]. 传感器与微系统,2008,27(12):102-105. ZHOU Yan,GAO Yang,LIU Tingting,et al. Numerical simulation of high-voltage switchgear panel contact temperature[J]. Transducer and Microsystem Technologies,2008,27(12): 102-105.
[15]  李伟力,丁树业,靳慧勇.基于耦合场的大型同步发电机定子温度场的数值计算[J]. 中国电机工程学报,2005,25(13):129-134. LI Weili,DING Shuye,JIN Huiyong. Numerical calculation of large synchronous generator stator temperature fields based on coupled fields[J]. Proceedings of the CSEE,2005,25(13): 129-134.
[16]  高 杨,周 岩,刘婷婷,等.高压开关柜的三维电磁场数值仿真[J]. 信息与电子工程,2009,7(6):540-544. GAO Yang,ZHOU Yan,LIU Tingting,et al. 3-D numerical simulation of electromagnetic field in HV switchgear cabinet[J]. Information and Electronic Engineering,2009,7(6): 540-544.
[17]  王有元,李寅伟,陆国俊,等.开关柜局部放电暂态对地电压传播特性的仿真分析[J]. 高电压技术,2011,37(7):1683-1688. WANG Youyuan,LI Yinwei,LU Guojun,et al. Simulation of transient earth voltages aroused by partial discharge in switchgears[J]. High Voltage Engineering,2011,37(7): 1683-1688.
[18]  徐建源,任春为,司秉娥,等.40.5 kV SF6充气式开关柜三维电场分析[J]. 中国电机工程学报,2008,28(15):136-140. XU Jianyuan,REN Chunwei,SI Bing’e,et al. Three dimensional electric field analysis of 40.5 kV SF6 cubicle gas-insulated metal-enclosed switchgear[J]. Proceedings of the CSEE,2008,28(15): 136-140.
[19]  JIA J,MENG J. Partial discharge impulsive noise in electricity substations and the impact on 2.4 GHz and 915 MHz ZigBee communications[C]//Power and Energy Society General Meeting(PES). Washington DC,USA: IEEE,2013: 1-5.

Full-Text

Contact Us

service@oalib.com

QQ:3279437679

WhatsApp +8615387084133