采用背靠背变流器接入配电网改善低压微网电压质量的控制设计

, PP. 171-181

Keywords: 微网,电压质量,不对称运行,背靠背变流器

Full-Text   Cite this paper   Add to My Lib

Abstract:

为消除配网不对称运行引起的微网电压不平衡,提出了一种采用背靠背变流器接入配网以改善低压微网电压质量的综合控制方案。基于二阶广义积分器推导αβ坐标系n次谐波瞬时正负序分量分解算法;电网侧变流器采用V/δ控制维持直流母线电压恒定,电压外环引入虚拟电抗以提高低压阻性线路的调节性能,根据不平衡电压条件下变流器输出功率波动特性,增加内环负序电流补偿减小配网不对称运行时直流电压的倍频波动;微网侧变流器采用电压外环电流内环双闭环定V/f控制,加入负序和三次谐波电压控制环节有效消除了微网公共连接点的电压不平衡。采用PSCAD/EMTDC仿真验证了本文所提控制方案的正确性和有效性。

References

[1]  Majumder R, Ghosh A, Ledwich G, et al. Power management and power flow control with back-to- back converters in a utility connected microgrid[J]. IEEE Transactions on Power Systems, 2010, 25(2): 821-834.
[2]  Abdel-Rahim N, Quaicoe J E. Three-phase voltage- source UPS inverter with voltage-controlled current- regulated feedback control scheme[C]. Proceedings of the 20th International Conference on Industrial Electronics, Control and Instrumentation, California, United States, 1994.
[3]  涂春鸣, 李慧, 唐杰, 等. 电网电压不对称对D-STATCOM的影响分析及抑制[J]. 电工技术学报, 2009, 24(8): 114-121.
[4]  Lasseter R H, Paigi P. Microgrid: a conceptual solution[C]. Proceedings of IEEE Annual Power Electronics Specialists Conference, Aachen, Germany, 2004.
[5]  周念成, 池源, 王强钢. 含非线性及不平衡负荷的微电网控制策略[J]. 电力系统自动化, 2011, 35(9): 61-66.
[6]  Vilathgamuwa D M, Loh P C, Li Yunwei. Protection of microgrids during utility voltage sags[J]. IEEE Transactions on Industrial Electronics, 2006, 53(5): 1427-1436.
[7]  Li Yunwei, Vilathgamuwa D M, Loh P C. Microgrid power quality enhancement using a three-phase four-wire grid-interfacing compensator[J]. IEEE Transactions on Industry Applications, 2005, 41(6): 1707-1719.
[8]  Li Yunwei, Vilathgamuwa D M, Loh P C. A grid- interfacing power quality compensator for three-phase three-wire microgrid application[J]. IEEE Transactions on Power Electronics, 2006, 21(4): 1021-1031.
[9]  Wang F, Duarte J, Hendrix M. Grid-interfacing converter systems with enhanced voltage quality for microgrid application-concept and implementation[J]. IEEE Transactions on Power Electronics, 2011, 26(12): 3501-3513.
[10]  Rodriguez P, Timbus A V, Teodorescu Remus, et al. Flexible active power control of distributed power generation systems during grid faults[J]. IEEE Transactions on Industrial Electronics, 2007, 54(5): 2583-2592.
[11]  De Brabandere K, Bolsens B, Van den Keybus J, et al. A voltage and frequency droop control method for parallel inverters[J]. IEEE Transactions on Power Electronics, 2007, 22(4): 1107-1115.
[12]  Matas J, Castilla M, De Vicuña L G, et al. Virtual impedance loop for droop-controlled single-phase parallel inverters using a second-order general- integrator scheme[J]. IEEE Transactions on Power Electronics, 2010, 25(12): 2993-3002.
[13]  Akagi H, Kanazawa Y, Nabae A. Instantaneous reactive power compensators comprising switching devices without energy storage components[J]. IEEE Transactions on Industry Applications, 1984, 20(3): 625-630.
[14]  Hu Jiabing, He Yikang. Modeling and control of grid-connected voltage-sourced converters under generalized unbalanced operation conditions[J]. IEEE Transactions on Energy Conversion, 2008, 23(3): 903-913.
[15]  Lyon W V. Transient analysis of alternating-current machinery[M]. New York:John Wiley and Sons, 1954.
[16]  周国梁, 石新春, 付超, 等. VSC-HVDC离散模型及其不平衡控制策略[J]. 电工技术学报, 2008, 23(12): 137-143, 159.