全部 标题 作者
关键词 摘要

OALib Journal期刊
ISSN: 2333-9721
费用:99美元

查看量下载量

相关文章

更多...

变压器绕组变形在线监测实验研究

, PP. 184-190

Keywords: 绕组变形,高频电流传感器,电流偏差系数,电力变压器,在线监测

Full-Text   Cite this paper   Add to My Lib

Abstract:

变压器是电力系统最重要的设备之一,绕组故障是导致变压器故障的一个重要方面。本文采用了一种简单且有效的方法探讨了在线监测变压器绕组变形。在绕组首端通过套管注入一个频率在600kHz~1.2MHz之间的正弦信号,通过研制的高频电流传感器同时测量绕组首端和末端的高频电流信号,利用模拟滤波及数字滤波技术得到所施加的高频正弦信号,计算电流偏移量以确定绕组变形的程度,计算电流偏差系数以确定绕组变形的类型及位置。自制的高频电流传感器具有频带宽、线性度好及灵敏度高的优点。实验结果表明该方法能够实现变压器绕组变形的在线监测,并能够判别绕组变形的程度、类型,且电流偏差系数与绕组变形的位置有关,该方法灵敏度高,重复性好,抗干扰性强。

References

[1]  刘梦娜,彭发东,柯春俊,等. 变压器绕组变形故障的诊断分析[J]. 广东电力,2012,25(11): 108-111.
[2]  Bagheri M,Naderi M S,Blackburn T,et al. On-line transformer winding deformation diagnosis: a profound insight to methods[C]. 26th International Power System Conference,2011: 1-14.
[3]  吴立增,朱永利,苑津莎. 基于贝叶斯网络分类器的变压器综合故障诊断方法[J]. 电工技术学报,2005,20(04): 45-51.
[4]  Wu Lizeng,Zhu Yongli,Yuan Jinsha. Novel method for transformer faults intigrted diagnosis on bayesian network classifier[J]. Transactions of China Electro- tecnical Society,2005,20(04): 45-51.
[5]  王钰,李彦明,张成良. 变压器绕组变形检测的LVI法和FRA法的比较研究[J]. 高电压技术,1997,23(01): 13-15.
[6]  Pham D A K,Pham T M T,Safari M H,et al. FRA-based transformer parameters at low frequencies [C]. IEEE International Conference on High Voltage Engineering and Application (ICHVE),2012: 476-479.
[7]  Florkowski M,Furgał J. Modelling of winding failures identification using the frequency response analysis (FRA) method[J]. Electric Power Systems Research,2009,79(7): 1069-1075.
[8]  Satish L,Sahoo S K. Locating faults in a transformer winding: An experimental study[J]. Electric Power Systems Research,2009,79(1): 89-97.
[9]  Oguz Soysal A. A method for wide frequency range modeling of power transformers and rotating machines [J]. IEEE Transactions on Power Delivery,1993,8(4): 1802-1810.
[10]  Joshi P M,Kulkarni S V. A novel approach for on-line deformation diagnostics of transformer windings[C]. IEEE Power and Energy Society General Meeting,2010: 1-6.
[11]  Wang M,Vandermaar A J,Srivastava K. Improved detection of power transformer winding movement by extending the FRA high frequency range[J]. IEEE Transactions on Power Delivery,2005,20(3): 1930- 1938.
[12]  Setayeshmehr A,Akbari A,Borsi H,et al. New sensors for on-line monitoring of power transformer bushings [C]. Nordic Insulation Symposium,2005: 151-154.
[13]  Liu Mengna,Peng Fadong,Ke Chunjun,et al. Diagnosis analysis on transformer winding deformation failure[J]. Guangdong Electric Power,2012,25(11): 108-111.
[14]  Wang Jue,Li Yanming,Zhang Chengliang. The comparisonal study on LVI and FRA method of detecting winding deformation faults in transformers [J]. High Voltage Engineering,1997,23(01): 13-15.
[15]  徐大可,汲胜昌,李彦明. 变压器绕组变形在线监测的理论研究[J]. 高电压技术,2000,26(03): 16-18.
[16]  Xu Dake,Ji Shengchang,Li Yanming. A theorectical research on on-line monitoring of winding deformation of power transformer[J]. High Voltage Engineering,2000,26(03): 16-18.
[17]  刘兴平,陈民铀. 一种配电变压器绕组变形故障的在线监测新方法[J]. 电力系统保护与控制,2013,41(12): 20-26.
[18]  Liu Xingping,Chen Minyou. A novel method on on- line monitoring of winding deformation of transformers [J]. Power System Protection and Control,2013,41(12): 20-26.
[19]  Secue J,Mombello E. Sweep frequency response analysis(SFRA) for the assessment of winding displace- ments and deformation in power transformers[J]. Electric Power Systems Research,2008,78(6): 1119- 1128.
[20]  Joshi P M,Kulkarni S. Use of a deformation coefficient for transformer winding diagnostics[J]. International Journal of Emerging Electric Power Systems,2008,9(3): 1-15.
[21]  De Rybel T,Singh A,Vandermaar J A,et al. Apparatus for online power transformer winding monitoring using bushing tap injection[J]. IEEE Transactions on Power Delivery,2009,24(3): 996- 1003.
[22]  Setayeshmehr A,Borsi H,Gockenbach E,et al. On-line monitoring of transformer via transfer function [C]. Electrical Insulation Conference,2009: 278-282.
[23]  Akbari A,Borsi H,Gockenbach E,et al. Experiences with a non-invasive capacitive sensor for on-line partial discharge detection in power transformers[J]. Diagnostik Elektrischer Betriebsmittel: Vorträge der ETG-Fachtagung am 09. und 10. März in Köln,2004,97: 301-304.
[24]  Joshi P,Kulkarni S. A diagnostic method for deter- mining deformations in a transformer winding: India,2009069145[P]. 2009-06-04.

Full-Text

Contact Us

service@oalib.com

QQ:3279437679