用于VFTO测量的GIS窗口式传感器

, PP. 210-217

Keywords: GIS手孔,电容式传感器,快速暂态过电压,宽频带

Full-Text   Cite this paper   Add to My Lib

Abstract:

为了测量气体绝缘变电站中(GIS)开关操作引起的快速暂态过电压(VFTO),本文设计了一种基于GIS手孔的窗口式电压传感器。首先分析影响传感器高频特性和低频特性的各项因素,窗口式分压器的高压臂电感、电容参数主要影响传感器的高频特性,低压臂电容和后级等效阻抗构成的时间常数决定传感器的低频特性。其次测量了该传感器的幅频响应和方波响应,所设计传感器在10kHz~80MHz频带范围内的平直度在±1dB之内,其方波响应的固有响应时间小于1.75ns。最后在实验室进行了VFTO模拟实验,测试结果表明所研制的窗口式传感器可以有效地测量GIS中击穿形成的快速暂态现象。

References

[1]  Mepplelink J, Diederich K, Feser K, et al. Very fast transients in GIS[J]. IEEE Transactions on Power Delivery, 1989, 4(1): 223-233.
[2]  谷定燮, 修木洪, 戴敏. 1000kV GIS变电所VFTO特性研究[J]. 高电压技术, 2007, 33(11): 27-32.
[3]  Gu Dingxie, Xiu Muhong, Dai Min. Study on VFTO of 1 000kV GIS substation[J]. High Voltage Engineering, 2007, 33(11): 27-32.
[4]  Chen Weijiang, Yan Xianglian, Wang Shaowu. Recent progress in investigations on very fast transient overvoltage in gas insulated switchgear[J]. Proceedings of the CSEE, 2011, 31(31): 1-11.
[5]  岳功昌, 刘卫东, 陈维江. 气体绝缘开关设备中特快速瞬态过电压的全过程测量方法[J]. 中国电机工程学报, 2011, 31(31): 18-27.
[6]  Yue Gongchang, Liu Weidong, Chen Weijiang. Measurement methods of very fast transient overvoltage in gas insulated switchgear with complete process[J]. Proceedings of the CSEE, 2011, 31(31): 18-27.
[7]  Nojima K, Nishiwki S, Okubo H, et al. Measurement of surge current and voltage waveforms using optical-transmission technique[J]. IEE Proceedings C Generation, Transmission & Distribution, 1987, 134(6): 415-422.
[8]  Raković D. Materials Science[M]. Naučna Knjiga, Beograd, Yugoslavia, 1994.
[9]  Working Group 33/13209. Very fast transient phenomena associated with gas insulated substations: CIGRE Report 33213[R]. Paris, France, 1998.
[10]  陈维江, 颜湘莲, 王绍武. 气体绝缘开关设备中特快速瞬态过电压研究的新进展[J]. 中国电机工程学报, 2011, 31(31): 1-11.
[11]  Boggs S A, Fujimoto N. Techniques and instrument for measurement of transients in gas insulated switchgear[J]. IEEE Transactions on Electrical Insulation , 1984, 19(2): 87-92.
[12]  Shihab S. A fast response impulse voltage measuring system for testing of gas insulated substation equipment[J]. IEEE Transaction on Power Delivery, 1986, 1(3): 42-47.
[13]  史保壮, 张文元, 邱毓昌. 测量气体绝缘变电站中快速暂态过电压的微分积分方法[J]. 中国电机工程学报, 1999, 19(5): 59-61, 29.
[14]  Shi Baozhuang, Zhang Wenyuan, Qiu Yuchang. Differentiating/integrating system for the measurement of very fast transient overvoltages in GIS[J]. Proceedings of the CSEE, 1999, 19(5): 59-61, 29.
[15]  Christian J, Xie J. Very fast transient oscillation measurement at three gorges left bank hydro power plant[C]. International Conference on Power System Technology, 2006.
[16]  Yanabu S, Murase H, Aoyagi H, et al. Estimation of fast transient overvoltage in gas-insulated substation[J]. IEEE Transaction on Power Delivery, 1990, 5(4): 1875-1882.
[17]  High voltage test techniques with very fast impulses, part 1: measuring systems for very fast front overvoltages generated in gas insulated substations[S]. IEC1321-1, 1994.
[18]  陈维江, 李志兵, 孙岗, 等. 特高压气体绝缘开关设备中特快速瞬态过电压特性的试验研究[J], 中国电机工程学报. 2011, 31(31): 38-47.
[19]  Chen Weijiang, Li Zhibing, Sun Gang, et al. Experimental research on the characteristics of very fast transient overvoltage in ultra high voltage gas insulated switchgear[J]. Proceedings of the CSEE 2011, 31(31): 38-47.