电网非理想情况下的双馈风电机组锁相控制

, PP. 240-247

Keywords: 锁相环,电网非理想,风力发电,控制设计

Full-Text   Cite this paper   Add to My Lib

Abstract:

随着风力发电规模的不断增加,电网非理想情况下的风电机组并网运行性能成为研究的重点。为保证双馈风电机组在电网非理想情况时能够准确、快速地跟踪电网的相位和频率,提出了一种基于abc坐标系延时算法的dq锁相方法。该方法在传统的软件锁相方法基础上,利用延时信号算法来消除由电压不对称所引入的锁相环路二次波动量,通过合理设计环路滤波器来增加锁相环路对电网5、7次谐波量的衰减系数。仿真和实验结果表明,该锁相方法不仅能很好地抑制电网三相不对称和畸变所引起的锁相环相位波动,同时也获得了较好的动态性能,能够在电网发生故障时快速地跟踪电网相位和频率,可为电网非理想情况下双馈风电机组的可靠运行提供准确的电网频率和相位信息。AbstractWithincreaseofinstalledwindpowercapacity,theoperationperformanceofwindpowersystemundernon-idealgridconditionshasbecomearesearchemphasis.Inordertotrackphaseand从frequencyofgridaccuratelyandquickly,thispaperpresentsanewphaselockedloop(PLL)methodbyusingdelaysignalcancellationintheabccoordinatesystem.BasedonthetraditionalmethodofsoftwarePLL,thedelaysignalcancellationalgorithmisusedtoeliminatethesecondfluctuationofthecontrolloopunderunbalancedgridcondition.AdesignmethodforthePLLloopcontrollerisalsodevelopedinordertoincreasetheattenuationcoefficientof5thand7thharmonics.SimulationandexperimentalresultsshowthattheproposedPLLsystemnotonlyeffectivelyattenuatestheloopfluctuationwhichiscausedbynon-idealgrid,butalsoobtaingooddynamicperformance.ThePLLsystemcanprovideaccuratephaseandfrequencyinformationforsafeandreliableoperationofwindturbinesundergridfaults.

References

[1]  贺益康, 周鹏. 变速恒频双馈异步风力发电系统低电压穿越技术综述[J]. 电工技术学报, 2009, 24(9): 140-145.
[2]  He Yikang, Zhou Peng. Overview of low voltage ride-through technology for variable speed constant frequency doubly fed wind power generation systems[J]. Transactions of China Electrotechnical Society, 2009, 24(9): 140-145.
[3]  Xu Lie. Coordinated control of DFIG’s rotor and grid side converters during network unbalance[J]. IEEE Transactions on Power Electronics, 2008, 23(3): 1041-1049.
[4]  Hu Jiabing, He Yikang, Xu Lie, et al. Improved control of DFIG systems during network unbalance using PI-R current regulators[J]. IEEE Transactions on Industrial Electronics, 2009, 56(2): 439-451.
[5]  Zhou Peng, He Yikang, Hu Jiabing. Detection of voltage synchronization signals for a wind energy generation system unbalanced grid conditions[J]. Transactions of China Electrotechnical Society, 2008, 23(5): 108-113.
[6]  周国梁, 石新春, 付超. 三相电压畸变条件下软件锁相环分析与实现[J]. 电力电子技术, 2007, 41(7): 47-49.
[7]  Chung Se-Kyo. A phase tracking system for three phase utility interface inverters[J]. IEEE Transactions on Power Electronics, 2000, 15(3): 431-438.
[8]  Zhan C, Fitzer C, Ramachandaramurthy V K, et al. Software phase-locked loop applied to dynamic voltage restorer(DVR)[C]. 2001 IEEE Power Engineering Society Winter Meeting, 2001: 1033-1038.
[9]  Wu Longhui, Zhuo Fang, Wang Zhaoan. Soft phase locked loop for active power filter applied in small rating stand-alone power system[C]. 2007 IEEE Power Electronics Specialists Conference, 2007: 2600-2606.
[10]  Bueno E J, Rodriguez F J, Espinosa F, et al. SPLL design to flux oriented of a VSC interface for wind power applications[C]. The 31th Annual Conference of the IEEE Industrial Electronics Society, 2005: 2451-2456.
[11]  Clemens J, Julija M, Thomas A, et al. International comparison of requirements for connection of wind turbines to power systems[J]. Wind Energy, 2005, 8(3): 295-306.
[12]  Kiani M, Lee W. Effects of voltage unbalance and system harmonics on the performance of doubly fed induction wind generators[C]. 2008 IEEE Industry Applications Society Annual Meeting, 2008: 1-7.
[13]  周鹏, 贺益康, 胡家兵. 电网不平衡状态下风电机组运行控制中电压同步信号的检测[J]. 电工技术学报, 2008, 23(5): 108-113.
[14]  Zhou Guoliang, Shi Xinchun, Fu Chao. Operation of a software phase locked loop under distorted three-phase voltage[J]. Power Electronics, 2007, 41(7): 47-49.
[15]  Kaura V, Blasko V. Operation of a phase locked loop system under distorted utility conditions[J]. IEEE Transactions on Industry Applications, 1997, 33(1): 58-63.
[16]  Saccomando G, Svensson J. Transient operation of grid-connected voltage source converter under unbalanced voltage conditions[C]. 2001 IEEE Industry Applications Conference, 2001: 2419-2424.
[17]  邱关源. 电路[M]. 4版. 北京: 高等教育出版社, 1999.
[18]  Rioual P, Pouliquen H, Louis J P. Regulation of a PWM rectifier in the unbalanced network state[C]. 1993 IEEE Power Electronics Specialists Conference, 1993: 641-647.
[19]  Rodriguez P, Luna A, Ciobotaru M, et al. Advanced grid synchronization system for power converters under unbalanced and distorted operating conditions[C]. The 32th Annual Conference of the IEEE Industrial Electronics Society, 2006: 5173-5178.