化工学报  2015 

空调送风速度和送风角度对可燃性冷媒R32泄漏扩散规律的影响

DOI: 10.11949/j.issn.0438-1157.20141782, PP. 2351-2358

Keywords: R32,泄漏,送风速度,送风角度,对流作用,扩散,安全性

Full-Text   Cite this paper   Add to My Lib

Abstract:

R32以其良好的热力性能和环保特性成为了极具潜力的替代制冷剂,然而其可燃性制约了它的广泛应用。从可燃性冷媒R32的泄漏扩散对室内安全性影响的角度出发,采用实验研究的方法,探索空调运行条件下制冷剂泄漏规律及空调送风速度和送风角度对室内R32浓度分布的影响。分析结果表明,空调运行时制冷剂泄漏速率随时间逐渐降低,泄漏过程可以分为高速泄漏阶段和低速泄漏阶段;分析空调送风速度和送风角度对室内R32浓度分布的影响,得到不同送风工况下室内R32的浓度分布规律;对制冷剂泄漏条件下室内环境安全性进行评价,结果表明在R32开始泄漏的很短时间内,泄漏口附近出现可燃区域,但可燃区域滞留时间很短,危险性较小。

References

[1]  Atul S Padalkar, Kundlik V Mali, Sukumar Devotta. Simulated and experimental performance of split packaged air conditioner using refrigerant HC-290 as a substitute for HCFC-22 [J]. Applied Thermal Engineering, 2014, 62: 277-284.
[2]  Dalkilic A S, Wongwises S. A performance comparison of vapour-compression refrigeration system using various alternative refrigerants [J]. International Communications in Heat and Mass Transfer, 2010, 37: 1340-1349.
[3]  Devotta S, Waghmare A V, Sawant N N, Domkundwar B M. Alternatives to HCFC-22 for air conditioners [J]. Applied Thermal Engineering, 2001, 21: 703-715.
[4]  Yang Zhao(杨昭), Peng Jijun(彭继军), Zhang Furen(张甫仁). Dynamic process analysis of pure refrigerant leakage from a tin [J]. Fluid Machinery(流体机械), 2006, 34(1): 63-68.
[5]  Yang Zhao(杨昭), Peng Jijun(彭继军), Zhang Furen(张甫仁). Finite-time diffusion models of leaked refrigerant [J]. Journal of Tianjin University(天津大学学报), 2006, 39(6): 657-662.
[6]  Li Tingxun(李廷勋), Liang Jierong(梁杰荣). Testing research on indoor R290 RAC leakage// 2010 China Household Electrical Appliances Technology Conference[C]. Hefei, 2010.
[7]  Li Tingxun. Indoor leakage test for safety of R-290 split type room air conditioner [J]. International Journal of Refrigeration, 2014, 40: 380-389.
[8]  Liu Zhixin(刘知新), Guo Chunhui(郭春辉), Liu Chang(刘畅), Xu Chen(许晨), Xu Yong'en(徐永恩). Experimental research on leakage and security of R290 household air conditioner [J].Refrigeration and Air-conditioning(制冷空调), 2010, 10(5): 49-51.
[9]  Li Yunong, Tao Junjun, Han Yuchong, Han Xue, Qin Jun. Numerical and experimental study on the diffusion property of difluoromethane (HFC-32) in leakage [J]. Procedia Engineering, 2014, (71): 34-43.
[10]  Zhang Wang(张网), Yang Zhao(杨昭), Wang Jie(王婕), Lü Dong(吕东), Zhong Zhifeng(钟志锋). Leakage research of split-type air-conditioner using R290 as refrigerant [J]. Journal of Refrigeration(制冷学报), 2013, 34(6): 42-47.
[11]  Xu Shuaishuai(徐帅帅), Zhong Maohua(钟茂华), Shi Congling(史聪灵), Liu Shuangqing(刘双庆). Analysis on risks by leakage of HFC-32 refrigerant [J]. Journal of Safety Science and Technology(中国安全生产科学技术), 2014, 10(4): 69-73.
[12]  Colbourne D, Suen K O. Appraising the flammability hazards of hydrocarbon refrigerants using quantitative risk assessment model(Ⅰ): Modelling approach [J]. International Journal of Refrigeration, 2004, 27: 774-783.
[13]  Colbourne D, Suen K O. Appraising the flammability hazards of hydrocarbon refrigerants using quantitative risk assessment model(Ⅱ): Model evaluation and analysis [J]. International Journal of Refrigeration, 2004, 27: 784-793.
[14]  Tian Guansan(田贯三), Yang Zhao(杨昭), Liu Wanfu(刘万福), Ma Yitai(马一太). Analysis and assessment on the explosive hazards of leakage flammable refrigerants [J]. Journal of Safety and Environment(安全与环境学报), 2001, 1(6): 39-43.
[15]  Zhang Wang, Yang Zhao, Li Jin, Ren Changxing, Lv Dong, Wang Jie, Zhang Xin, Wu Wei. Research on the flammability hazards of an air conditioner using refrigerant R-290 [J]. International Journal of Refrigeration, 2013, 36: 1483-1494.
[16]  Cheong K W, Riffat S B. Monitoring hydrofluorocarbon refrigerant leakage from air-conditioning systems in buildings [J]. Applied Energy, 1996, 53:341-347.
[17]  Yajmar, Moriwaki M, Sugawa O, Imamura T. Experimental safety evaluation on flammability of R32 refrigerant// International Congress of Refrigeration[C]. Pragwe,2011.
[18]  Eiji Hihara, Tatsuhito Hattori. Progress of the University of Tokyo//Risk Assessment of Mildly Flammable Refrigerants 2012 Progress[C]. Tokyo, 2013: 13-29.
[19]  Andrew Gigiel. Safety testing of domestic refrigerators using flammable refrigerants [J]. International Journal of Refrigeration, 2004, 27: 621-628.
[20]  Liu Quanyi, Zhang Hui, Liu Yi, Huang Hong, Zhang Xiaole, Li Zhipeng, Yao Wei. Influencing factors of flammable refrigerants leaking in building air conditioning system [J]. Procedia Engineering, 2013, 62: 648-654.
[21]  Liu Quanyi (刘全义), Zhang Hui (张辉), Liu Yi(刘奕), Li Zhipeng (李志鹏). Concentration distribution of leaking flammable refrigerants from building air conditioning systems [J]. J. Tsinghua Univ.: Sci. & Technol. (清华大学学报:自然科学版), 2013, 53(9): 20-26.