Abstract:

基于对空气源热泵结霜机理的研究,从抑制结霜的两个条件出发,提出了无霜空气源热泵新系统。选取适用于该系统的喷淋溶液,搭建了实验台。通过实验验证,证明此系统具有可行性。"防霜"模式运行时,送风温差比常规系统高1.5℃,供热量高6%,且送风参数稳定,运行过程中,压缩比基本保持不变,压缩机和系统稳定性高。选用甘油水溶液作为喷淋溶液时,为保证防霜效果,甘油质量分数应在31%~65%;单位迎风面积喷淋流量应在0.53~0.64t·(h·m2)-1。

References

[1]  Zhang Jianzhong(张建忠),Gong Yanfeng(龚延风).Air source heat pump chiller unit in Nanjing[J].Modern Air Conditioning(现代空调),2001(3):141-156
[2]  Byun J S,Lee J,Jeon C D.Frost retardation of an air-source heat pump by the hot gas bypass method [J]. International Journal of Refrigeration,2002,25:405-413
[3]  O’Neal D L,Tree D R.A review of frost formation in simple geometries[J].ASHRAE Transactions,1985,91:267-281
[4]  Kondepudi S N,O’neal D L.Effect of different fin configu-ration on the performance of finned-tube heat exchanger under frosting conditions [J].ASHRAE Transactions,1990,96(2):439-444
[5]  Kondepudi S N,O’neal D L.Frosting performance of tube fin heat exchanger with wavy and corrugated fins [J]. Experimental Thermal and Fluid Science,1991,4:613-618
[6]  Yao Yang(姚杨),Ma Zuiliang(马最良).Frosting in winter for air source heat pump heat/chiller unit[J].Journal of Harbin University of Civil Engineering and Architecture(哈尔滨工业大学学报),2002,35(5):66-69
[7]  Han Zhitao(韩志涛),Yao Yang(姚杨),Jiang Yiqiang(姜益强).Status and development of air source heat pump hot gas defrosting research[J].Fluid Machinery(流体机械),2007,35(7):67-72
[8]  Hu Wenju,Jiang Yiqiang,Yao Yang.A novel thermal energy storage based reversed-cycle defrosting technology for air-to-air heat pumps//Proceedings of the International Conference on Cryogenics and Refrigeration[C].Shanghai,China,2008,5:755-759
[9]  Kondepudi S N,Murali K,Bhalerao A.Voiding HP evapo-rator frost through the use of desiccants//Proceeding of ASME-JSES-JSME International Solar Energy Conference[C].New York,1995:25-29
[10]  Wang S W,Liu Z Y.A new method for preventing HP from frosting [J].Renewable Energy,2005,30:753-761
[11]  Wang Yang(王洋),Jiang Huimin(江辉民),Ma Zuiliang(马最良).Experiment and analysis of delaying frost of air-source heat pump water chiller-heater units by increasing the evaporator area[J].Heating Ventilating & Air Conditioning(暖通空调),2006,36(7):83-87 target="_blank">
[12]  Gu Bo(谷波),Tian Shubo(田树波),Sun Tao(孙涛). Study on the frosting performance of air cooled heat pump units[J].Heating Ventilating & Air Conditioning(暖通空调),2001,31(1):81-82 target="_blank">
[13]  Nikulshina D G,Dol’skaya V L,Soigolina L S,et al. Investigation of energy characteristics of air coolers with ceramic-organic coating[J].Refrig. Tech.,1984(10):19-21
[14]  Seki N,Fukusako S,Matsuo K,et al.Incipient phenomena of frost formation[J].Bulletin of the JSME,1984,27(233):2476-2482
[15]  Jhee S,Lee K S,Kim W S.Effect of surface treatments on the frosting/defrosting behavior of a fin-tube heat exchanger[J].International Journal of Refrigeration,2002,25(8):1047-1053
[16]  Highgate D,Knight C,Probert S D.Anomalous freezing of water in hydrophilic polymeric structures [J].Applied Energy,1989,34(4):243-259