Accurate fault location algorithm on power transmission lines with use of two-end unsynchronized measurements

DOI: 10.2298/sjee1202189m

Keywords: fault location , unsynchronized measurements , communication , MATLAB

Full-Text   Cite this paper   Add to My Lib

Abstract:

This paper presents a new approach to fault location on power transmission lines. This approach uses two-end unsynchronised measurements of the line and benefits from the advantages of digital technology and numerical relaying, which are available today and can easily be applied for off-line analysis. The approach is to modify the apparent impedance method using a very simple first-order formula. The new method is independent of fault resistance, source impedances and pre-fault currents. In addition, the data volume communicated between relays is sufficiently small enough to be transmitted easily using a digital protection channel. The proposed approach is tested via digital simulation using MATLand the applied test results corroborate the superior performance of the proposed approach.