All Title Author
Keywords Abstract


A Novel Method on Fault Ride-Through of a DFIG Wind Turbine using a Dynamic Voltage Restorer During Symmetrical and Asymmetrical Grid Faults

Keywords: Doubly fed induction generator DFIG , dynamic voltage restorer DVR , fault ride-through and wind energy

Full-Text   Cite this paper   Add to My Lib

Abstract:

The application of a dynamic voltage restorer (DVR) connected to a wind-turbine-driven doubly fed induction generator (DFIG) is investigated. The setup allows the wind turbine system an uninterruptible fault ride-through of voltage dips. The DVR can compensate the faulty line voltage, while the DFIG wind turbine can continue its nominal operation as demanded in actual grid codes. Simulation results for a 2 MW wind turbine and measurement results on a 22 kW laboratory setup are presented, especially for asymmetrical grid faults. They show the effectiveness of the DVR in comparison to the low-voltage ride-through of the DFIG using a crowbar that does not allow continuous reactive power production.

Full-Text

comments powered by Disqus