电力系统自动化 2012
Impacts of Large-scale Wind Power Grid Integration onRelay Protection and CountermeasuresKeywords: wind,power,tripping,countermeasure,relay,protection Abstract: Severallarge-scalewindturbinetrippingaccidentsoccurredinJiuquanwindpowerbasein2011.Accordingtotheon-sitesurveyandanalysisoftheseaccidentsrelatedtorelayprotection,causeswerefoundtobethecollectionsystemdefectsandlowcorrectoperationrateofsmallcurrentgroundedlineselectorsoftheunearthedneutralpointcollectionsystem.ByreferringtoboththecharacteristicsofJiuquanwindpowerbaseandarrangementofrelayprotection,theshort-circuitfeaturesofwindpoweranditsimpactsonrelayprotectionareanalyzed.Thecollectionsystemandtheretrofitofthesmallcurrentgroundedlineselectorareimprovedbyspecificcountermeasures.Finally,furtherresearchsubjectsareputforward.
|