吸附剂对局部放电下SF6分解特征组分的吸附研究

DOI: 10.13334/j.0258-8013.pcsee.2014.03.021, PP. 486-494

Keywords: 吸附剂,局部放电,分解特性,特征组分,故障诊断

Full-Text   Cite this paper   Add to My Lib

Abstract:

为了保障SF6绝缘气体的纯度,需要在SF6气体绝缘设备气室中配置一定量的吸附剂,一方面用于控制气室内的水分含量,另一方面用于吸附因各种原因产生的杂质气体。因而,吸附剂的存在会对局部放电下使SF6发生分解而产生的特征组分进行吸附,使得特征组分含量和变化规律发生改变。在利用特征组分诊断气体绝缘设备内部故障时,必须考虑这一重要影响因素。为此,该文在搭建的SF6气体局部放电分解试验平台上,利用针–板电极产生局部放电(partialdischarge,PD)使SF6发生分解,采用气质联用仪定量测定放电室内特征组分的变化,获取不同吸附剂用量梯度下吸附特征组分的规律与特性。研究表明,无论有无放置吸附剂,在气室内都能检测到SOF4、SO2F2、SOF2和SO2等主要稳定特征组分,且随着吸附剂用量的增加,对特征组分的吸附率各不相同。

References

[1]  Van Brunt R J, Herron J T.Fundamental processes of SF6 decomposition and oxidation in glow and corona discharges[J].IEEE Transactions on Electrical Insulation.1990, 25(1):75-94.
[2]  Chu F Y.SF6 decomposition in gas-insulated equipment [J].IEEE Transactions on Electrical Insulation, 1986, 21(5):693-725.
[3]  邱毓昌.GIS装置及其绝缘技术[M].北京:水利水电出版社, 1994:101-116.Qiu Liuchang.GIS and its insulation technology[M].Beijing:China WaterPower Press, 1994:101-116 (in Chinese).
[4]  连鸿松.根据SF6气体分解产物诊断电气设备故障[J].福建电力与电工, 2005, 23(3):21-24.Lian Hongsong.Electrical equipment fault diagnosis according to SF6 department products[J].Fujian Power and Electrical Engineering, 2005, 23(3):21-24(in Chinese).
[5]  季严松, 王承玉, 杨韧, 等.SF6气体分解产物检测技术及其在GIS设备故障诊断中的应用[J].高压电器, 2011, 47(2):100-107.Ji Yansong, Wang Chengyu, Yang Ren, et al.Measuring technique of SF6 decomposition products and its application to fault diagnosis of GIS[J].High Voltage Apparatus, 2011, 47(2):100-107(in Chinese).
[6]  唐炬, 陈长杰, 刘帆, 等.局部放电下SF6分解组分检测与绝缘缺陷编码识别[J].电网技术, 2011, 35(1):110-116.Tang Ju, Chen Changjie, Liu Fan, et al.Detection of constituents from SF6 decomposition under partial discharge and recognition of insulation defect coding[J].Power System Technology, 2011, 35(1):110-116(in Chinese).
[7]  Tang Ju, Liu Fan, Zhang Xiaoxing, et al.Partial discharge recognition through an analysis of SF6 decomposition products Part 1 decomposition characteristics of SF6 under four different partial discharges[J].IEEE Transactions on Dielectrics and Electrical Insulation, 2012, 19(1):29-36.
[8]  Tang Ju, Liu Fan, Meng Qinghong, et al.Partial discharge recognition through an analysis of SF6 decomposition products, Part 2, feature extraction and decision tree-based pattern recognition[J].IEEE Transactions on Dielectrics and Electrical Insulation, 2012, 19(1):37-44.
[9]  Insulated Conductors Committee of the IEEE Power Engineering Society. IEEE Std 1125—1993 IEEE guide for moisture measurement and control in SF6 gas-insulated equipment[S].
[10]  Leeds W, Browne F, Strom A.The use of SF6-cor high power arc quenching[J].Power Apparatus and Systems, Part III.transactions of the american institute of electrical engineers, 1957, 76(6):906-909.
[11]  Tang Ju, Liu Fan, Zhang Xiaoxing, et al.Partial discharge recognition through an analysis of SF6 decomposition products Part 1 decomposition characteristics of sf6 under four different partial discharges[J].IEEE Transactions on Dielectrics and Electrical Insulation, 2012, 19(1):29-36.
[12]  Lussier T, Frechette M F, Rochefort A, et al.Interaction of SOF2 with Alumina and Zeolite 4A:a comparative study[C]//IEEE Annual Report-Conference on Electrical Insulation and Dielectric Phenomena, Millbrae, Canada, 1996.
[13]  Van brunt R J, Herron J T.Plasma chemical-model for decomposition of SF6 in a negative glow corona discharge[J].Physica Scripta, 1994, 53(2):9-29.
[14]  Van brunt R J.Physics and chemistry of partial discharge and corona-recent advances and future challenges[J].IEEE Transactions on Dielectrics and Electrical Insulation, 1994, 1(5):761-784.
[15]  孟玉婵, 朱芳菲.电气设备用六氟化硫的检测与监督[M].北京:中国电力出版社, 2009:201-204.Meng Yuchan, Zhu Fangfei.Electrical equipment with sulfur hexafluoride inspection and supervision[M].Beijing:China Power Press, 2009:201-204 (in Chinese).
[16]  徐如人, 庞文琴.分子筛与多孔材料化学[M].北京:科学出版社, 2004:145-155.Xu Ruren, Pang Wenqing.Molecular sieves and porous materials chemistry[M].Beijing:Science Press, 2004:145-155(in Chinese).
[17]  Tang Ju, Liu Fan, Meng Qinghong, et al.Partial discharge recognition through an analysis of sf6 decomposition products, Part 2, feature extraction and decision tree-based pattern recognition[J].IEEE Transactions on Dielectrics and Electrical Insulation, 2012, 19(1):37-44.
[18]  Piemontesi M, Niemeyer L.Sorption of SF6 and SF6 decomposition products by activated alumina and molecular sieve[C]//Conference Record of the 1996 IEEE International Symposium on Electrical Insulation.Montreal, Que:IEEE, 1996:828-838.
[19]  唐炬, 李涛, 万凌云, 等.SF6气体分解组份的多功能实验装置研制[J].高电压技术, 2008, 34(8):1583-1588.Tang Ju, Li Tao, Wan Lingyun, et al.Device of SF6 dissociation apparatus under partial discharge and gaseous decomposition components analysis system[J].High Voltage Technology, 2008, 34(8):1583-1588(in Chinese).
[20]  中华人民共和国电力工业部.DL/T 596—1996电力设备预防性实验规程[S].1996.Electric Power Industry Ministry of the People's Republic of China.DL/T596—1996 Preventive test code for electric power equipment[S].1996(in Chinese).