变压器油纸绝缘老化与水分含量评估频域介电特征量

, PP. 215-221

Keywords: 电力变压器,油纸绝缘,老化状态,水分含量,特征参量,FDS,介质损耗因数

Full-Text   Cite this paper   Add to My Lib

Abstract:

为区分水分以及老化状态对油纸绝缘频域介电响应的影响,更好地推动频域介电谱技术(FDS)应用于现场电力变压器绝缘状态的无损评估,首先在实验室制备了不同含水量、不同热老化状态的油纸绝缘样品,然后在深入分析老化和水分对频域介电响应影响规律的基础上,提出一种利用介质损耗因数tanδ区分油纸绝缘水分和老化状态对频域介电响应影响的方法,并提取了能够量化绝缘纸水分含量及聚合度的频域介电特征量。研究结果表明提取的油纸绝缘样品的频域介电特征量在10-1~10Hz的频域范围内对水分反映灵敏,而老化仅仅在10-3~10-1Hz的测试频段内对该特征量的影响较大,该特征量在两频段范围内的最大值分别与绝缘纸水分含量、聚合度均存在拟合优度较高的指数函数关系。提取的特征量可进一步应用于变压器油纸绝缘状态的无损评估。

References

[1]  Pahlavanpour P, Eklund, Martins M A.Insulating paper ageing and furfural formation[C]. Proceedings of Electrical Insulation and Electrical Manufacturing & Coil Winding Technology Conference, Indian- apolis, United States, 2003: 283-288.
[2]  Saha T K. Review of modern diagnostic techniques for assessing insulation condition in aged trans-
[3]  formers[J]. IEEE Transactions on Dielectrics and Electrical Insulation, 2003, 10(5): 903-917.
[4]  Zaengl W S. Application of dielectric spectroscopy intime and frequency domain for HV power equip-
[5]  ment[J]. IEEE Electrical Insulation Magazine, 2003, 19(6): 9-22.
[6]  Blennow J, Ekanayake C, Walczak K, et al. Field experiment with measurement of dielectric response in frequency domain for power transformer diagnostics[J]. IEEE Transactions on Dielectric and Electrical Insulation, 2006, 21(2): 681-688.
[7]  廖瑞金, 梁帅伟, 杨丽君, 等. 天然酯-普通纸(或热稳定纸)绝缘热老化特性[J]. 电工技术学报, 2009, 24(12): 12-17.
[8]  Liao Ruijin, Liang Shuaiwei, Yang Lijun, et al. Insulation thermal aging properties of natural ester immersed paper comparing with that of conventional and thermally upgraded papers[J]. Transactions of China Electrotechnical Society, 2009, 24(12): 12-17.
[9]  Emsley A M, Stevens G C. Review of chemical indicators of degradation of cellulosic electrical paper insulation in oil-filled transformers[J]. Proceedings of IEE Science, Measurement and Techno- logy, 1994, 141(5): 324-334.
[10]  Shroff D H, Stannett A W. Review of paper ageing in power transformers[J]. IEE Proceedings of Generation, Transmission and Distribution, 1985, 132(6): 312-319.
[11]  Kuang Y C, Chen G, Jarmm P. Recovery voltage measurement on oil-paper insulation with simple geometry and controlled environment[C]. Proceedings of the IEEE International Conference on Solid Diele- ctrics, Toulouse, France, 2004, 2: 739-742.
[12]  Saha T K, Purkait P. Investigation of polarization and depolarization current measurements for the assessment of oil-paper insulation of aged transformers[J]. IEEE Transactions on Dielectrics and Electrical Insulation, 2004, 11(1): 144-154.
[13]  Farahani M, Borsi H, Gockenbach E. Dielectric response studies on insulating system of high voltage rotating machines[J]. IEEE Transactions on Dielectrics and Electrical Insulation, 2006, 13(1): 383-393.
[14]  Yew J H, Pradhan M K, Saha T K. Effects of moisture and temperature on the frequency domain spectroscopy analysis of power transformer insulation[C]. IEEE Power Engineering Society General Meeting, Pittsburgh, USA, 2008: 1-8.
[15]  Liao R, Hao J, Chen G, et al. Quantitative analysis of ageing condition of oil-paper insulation by frequency domain spectroscopy[J]. IEEE Transactions on Dielectrics and Electrical Insulation, 2012, 19(3): 821-830.
[16]  廖瑞金, 郝建, 杨丽君, 等. 变压器油纸绝缘频域介电特征量与绝缘老化状态的关系[J]. 电工技术学报, 2012, 27(5): 43-49, 76.
[17]  Liao Ruijin, Hao Jian, Yang Lijun, et al. Relationship between frequency domain dielectric characteristic quantity and aging status of transformer oil-paper insulation[J]. Transactions of China Electrotechnical society, 2012, 27(5): 43-49, 76.
[18]  Ekanayake C, Gubanski S M, Graczkowski A, et al. Frequency response of oil impregnated pressboard and paper samples for estimating moisture in transformer insulation[J]. IEEE Transactions on Power Delivery, 2006, 21(3): 1309-1317.
[19]  魏建林, 王世强, 彭华东, 等. 变压器油纸绝缘的介电响应特性研究—加速热老化的介电谱[J]. 电工技术学报, 2012, 27(5): 56-62.
[20]  Wei Jianlin, Wang Shiqiang, Peng Huadong, et al. Investigation of dielectric response characteristics of transformer oil-paper insulation—dielectric spectroscopy of acceleratedly thermal aging[J]. Transactions of China Electrotechnical Society, 2012, 27(5): 56-62.
[21]  Saha T K, Purkait P. Investigations of temperature effects on the dielectric response measurements of transformer oil-paper insulation system[J]. IEEE Trans- actions on Power Delivery, 2008, 23(1): 252-260.
[22]  Setayeshmehr A, Fofana I, Akbari A, et al. Effect of temperature, water content and aging on the dielectric response of oil-impregnated paper[C]. IEEE Inter-
[23]  national Conference on Dielectric Liquids, France, 2008: 1-4.
[24]  Saha T K, Purkait P. Effects of temperature on time-domain dielectric diagnostics of transformers[C]. Institution of Engineers, Australia, 2004:157-162.
[25]  Gielniak J, Graczkowski A, Moranda H, et al. Moisture in cellulose insulation of power transformers-
[26]  statistics[J]. IEEE Transactions on Dielectrics and Electrical Insulation, 2013, 20(3): 981-987.
[27]  杨丽君, 廖瑞金, 孙会刚, 等. 变压器油纸绝缘热老化特性及特征量研究[J]. 电工技术学报, 2009, 24(8): 27-33.
[28]  Yang Lijun, Liao Ruijin, Sun Huigang, et al. Investi-
[29]  21 gation on properties and characteristics of oil-paper insulation in transformer during thermal degradation process[J]. Transactions of China Electrotechnical Society, 2009, 24(8): 27-33.
[30]  陈季丹, 刘子玉. 电介质物理学[M]. 北京: 机械工业出版社, 1982.
[31]  郝建, 廖瑞金, 杨丽君, 等. 应用频域介电谱法的变压器油纸绝缘老化状态评估[J]. 电网技术, 2011, 35(7): 187-193.
[32]  Hao Jian, Liao Ruijin, Yang Lijun, et al. Aging status assessment of power transformer oil-paper insulation by frequency-domain dielectric spectroscopy[J]. Power System Technology, 2011, 35(7): 187-193.

Full-Text

Contact Us

service@oalib.com

QQ:3279437679

WhatsApp +8615387084133