湿度对绞线正极性电晕电流脉冲及其无线电干扰影响的实验

, PP. 79-89

Keywords: 湿度,电晕电流脉冲,直流电晕,无线电干扰,功率谱

Full-Text   Cite this paper   Add to My Lib

Abstract:

为研究湿度对直流电晕无线电干扰的影响,搭建了直流绞线电晕放电实验平台,将相对湿度作为单一变化因素,使其在40%~85%范围内变化,采用试验导线终端匹配技术,通过准确测量直流绞线上的电晕电流脉冲,研究湿度对正极性电晕电流脉冲特性及其无线电干扰的影响。在湿度增加过程中,发现以下规律新的放电点会形成,但它们产生的电晕电流脉冲峰值通常较小;电晕电流脉冲的平均峰值减小;电晕电流脉冲重复频率先增加后减小,在相对湿度60%~75%达到最大;在相对湿度40%~60%范围内,电晕电流脉冲上升时间、半峰值时间及持续时间显著减小,而在60%~80%范围内,无明显变化规律;电晕电流脉冲功率谱减小,这也说明了湿度增加会使电晕电流脉冲产生的无线电干扰减小。

References

[1]  Khalifa M, El-Debeiky S. Analysis of the effect of humidity on d. c. corona power losses[J]. Proceedings of the Institution of Electrical Engineers, 1971, 118(5): 714-718.
[2]  Allen N L, Berger G, Dring D, et al. Effects of humidity on corona inception in a diverging electric field[J]. IEE Proceedings of a Physical Science, Measurement and Instrumentation, Management and Education- Reviews, 1981, 128(8): 565-570.
[3]  Fouad L, Elhazek S. Effect of humidity on positive corona discharge in a three electrode system[J]. Journal of Electrostatics, 1995, 35(1): 21-30.
[4]  Bian X M, Meng X B, Wang L M, et al. Negative corona inception voltages in rod-plane gaps at various air pressures and humidities[J]. IEEE Transactions on Dielectrics and Electrical Insulation, 2011, 18(2): 613-619.
[5]  惠建峰, 关志成, 王黎明, 等. 正直流电晕特性随气压和湿度变化的研究[J]. 中国电机工程学报, 2007, 27(33): 53-58. Hui Jianfeng, Guan Zhicheng, Wang Liming, et al. Research on variation of positive DC corona character- ristics with air pressure and humidity[J]. Proceedings of the CSEE, 2007, 27(33): 53-58.
[6]  卞星明, 惠建峰, 黄海鲲, 等. 气压湿度对负直流电晕特性影响的研究[J]. 中国电机工程学报, 2010, 30(4): 118-124. Bian Xingming, Hui Jianfeng, Huang Haikun, et al. Effects of air pressure and humidity on the charateristics of negative DC corona[J]. Proceedings of the CSEE, 2010, 30(4): 118-124.
[7]  Bian X M, Wang L M, MacAlpine J M K, et al. Positive corona inception voltages and corona currents for air at various pressures and humidities[J]. IEEE Transactions on Dielectrics and Electrical Insulation, 2010, 17(1): 63-70.
[8]  安冰, 丁燕生, 王伟, 等. 湿度对电晕笼中导线直流电晕特性的影响[J]. 电网技术, 2008, 32(24): 98-101. An Bing, Ding Yansheng, Wang Wei, et al. Influence of humidity on corona performance of DC conductor in corona cage[J]. Power System Technology, 2008, 32(24): 98-101.
[9]  Hu Q, Shu L, Jiang X, et al. Effects of air pressure and humidity on the corona onset voltage of bundle conductors[J]. IET Generation, Transmission & Distri- bution, 2011, 5(6): 621-629.
[10]  Xu M M, Tan Z Y, Li K J. Modified Peek formula for calculating positive DC corona inception electric field under variable humidity[J]. IEEE Transactions on Dielectrics and Electrical Insulation, 2012, 19(4): 1377-1382.
[11]  Wang X H, You C F. Effect of humidity on negative corona discharge of electrostatic precipitators[J]. IEEE Transactions on Dielectrics and Electrical Insulation, 2013, 20(5): 1720-1726.
[12]  Meng X B, Hui J F, Mei H W, et al. Influence of pressure and humidity on the amplitude-phase distribu- tion of AC corona pulse[C]. Annual Report Conference on Electrical Insulation and Dielectric Phenomena, 2013: 838-841.
[13]  Nouri H, Zouzou N, Moreau E, et al. Effect of relative humidity on current-voltage characteristics of an electrostatic precipitator[J]. Journal of Electrostatics, 2012, 70(1): 20-24.
[14]  Allen N L. Corona, breakdown and humidity in the rod- plane gap[J]. IEE Proceedings a Physical Science, Measurement and Instrumentation, Management and Education-Reviews,1986, 133(8): 562-568.
[15]  蒋虹, 陈豫朝, 张广洲, 等. 温湿度对交流电晕无线电干扰的影响[J]. 高电压技术, 2011, 37(12): 2918-2923. Jiang Hong, Chen Yuchao, Zhang Guangzhou, et al. Effect of temperature and humidity on radio interference generated from AC corona[J]. High Voltage Engineering, 2011, 37(12): 2918-2923.
[16]  Liu Yang, Cui Xiang, Lu Tiebing, et al. Accurate measurement of original current pulses because of positive corona in the coaxial cylindrical arrangement [J]. IET Science, Measurement & Technology, accepted.
[17]  张峰, 石现峰, 张学智. Welch功率谱估计算法仿真及分析[J]. 西安工业大学学报, 2009, 29(4): 353-356. Zhang Feng, Shi Xianfeng, Zhang Xuezhi. Study and simulation of Welch power spectrum estimation method [J]. Journal of Xi’an Technological University, 2009, 29(4): 353-356.
[18]  Malik N H, Al-rainy A A. Statistical variation of DC corona pulse amplitudes in point-to-plane air gaps[J]. IEEE Transactions on Electrical Insulation, 1987, EI-22(6): 825-829.
[19]  Maruvada P S. Corona performance of high-voltage transmission lines[M]. Baldock: Research Studies Press, 2000.
[20]  Chervenak J G, Van Lint V A J. Electron-ion recom- bination in air at EMP fields[J]. IEEE Transactions on Nuclear Science, 1985, 32(6): 4308-4311.
[21]  Sakata S, Okada T. Effect of humidity on hydrated cluster-ion formation in a clean room corona discharge neutralizer[J]. Journal of Aerosol Science, 1994, 25(5): 879-893.
[22]  Trinh N G. Partial discharge XIX: Discharge in air Part I: Physical mechanisms[J]. IEEE Electrical Insulation Magazine, 1995, 11(2): 23-29.
[23]  Nigol O. Analysis of radio noise from high-voltage lines I-meter response to corona pulses[J]. IEEE Transactions on Power Apparatus and Systems, 1964, 83(5): 524-533.
[24]  Boutlendj M, Allen N L, Lightfoot H A, et al. Positive DC corona and sparkover in short and long rod-plane gaps under variable humidity conditions[J]. IEE Proc. -A, 1991, 138(1): 31-36.
[25]  Rodriguez D, Gorur R S, Hansen P M. Effect of humidity on the breakdown characteristics of air in non-uniform fields at 30kHz[J]. IEEE Transactions on Dielectrics and Electrical Insulation, 2010, 17(1): 45-52.
[26]  Peyrous R. The effects of relative humidity on ozone production by corona discharge in oxygen or air-a numerical simulation-part I: oxygen[J]. Ozone Science and Engineering, 1990, 12(1): 19-40.
[27]  Peyrous R. The effects of relative humidity on ozone production by corona discharge in oxygen or air-a numerical simulation-part II: air[J]. Ozone Science and Engineering, 1990, 12(1): 41-64.
[28]  Chen J, Wang P. Effect of relative humidity on electron distribution and ozone production by DC coronas in air[J]. IEEE Transactions on Plasma Science, 2005, 33(2): 808-812.
[29]  Hui J F, Guan Z C, Wang L M, et al. Variation of the dynamics of positive streamer with pressure and humidity in air[J]. IEEE Transactions on Dielectrics and Electrical Insulation, 2008, 15(2): 382-389.
[30]  卞星明, 惠建峰, 黄海鲲, 等. 气压和湿度对正直流电晕流注脉冲特性的影响[J]. 高电压技术, 2009, 35(10): 2371-2382. Bian Xingming, Hui Jianfeng, Huang Haikun, et al. Influence of air pressure and humidity on positive DC corona streamer pulse characteristics[J]. High Voltage Engineering, 2009, 35(10): 2371-2382.
[31]  Otto A J. Direct current conductor corona modeling and metrology:[D]. Stellenbosch, South Africa: Univer- sity of Stellenbosch, 2009.
[32]  DL/T 691-1999, 高压架空送电线路无线电干扰计算方法[S].
[33]  Liao T W, Keen W A, Powell D R. Relationship between corona and radio influence on transmission lines, laboratory studies I-point and conductor corona [J]. Transactions of the American Institute of Electrical Engineers on Power Apparatus and Systems, Part III, 1954, 76(3): 530-538.
[34]  Maruvada P S, Hylten-Cavallius N, Chinh N T. Radio noise meter response to random pulses by computer simulation[J]. IEEE Transactions on Power Apparatus and Systems, 1974, 93(3): 905-915.
[35]  Maruvada P S, Trinh N G, Dallaire D, et al. Corona performance of a conductor bundle for bipolar HVDC transmission at ±750kV[J]. IEEE Transactions on Power Apparatus and Systems, 1977, 96(6): 1872-1882.
[36]  Maruvada P S, Trinh N G, Dallaire R D, et al. Corona studies for bipolar HVDC transmission at voltages between ±600kV and ±1 200kV Part 1: Long-term bipolar line studies[J]. IEEE Transactions on Power Apparatus and Systems, 1981, 100(3): 1453-1461.
[37]  Maruvada P S, Dallarie R D, Heroux P, et al. Corona studies for bipolar HVDC transmission at voltages between ±600kV and ±1200kV Part 2: Special bipolar line, bipolar cage and bus studies[J]. IEEE Transactions on Power Apparatus and Systems, 1981, 100(3): 1462- 1471.
[38]  Maruvada P S, Dallaire R D, Heroux P, et al. Long- term statistical study of the corona electrical field and ion-current performance of a ±900kV bipolar HVDC transmission line configuration[J]. IEEE Power Enginee- ring Review, 1984, 4(1): 33-33.

Full-Text

Contact Us

service@oalib.com

QQ:3279437679

WhatsApp +8615387084133