化工学报  2015 

低温吸湿复合吸附剂的制备及吸湿性能

DOI: 10.11949/j.issn.0438-1157.20150297, PP. 154-158

Keywords: 低温,复合吸附剂,制备,吸湿性能

Full-Text   Cite this paper   Add to My Lib

Abstract:

针对冷库结霜严重制约其经济性的问题,化学固体吸附除湿防霜技术逐渐得到重视。本文将对水吸附能力较强的金属卤化物与容易定型且传热传质性能较好的分子筛相结合,制成复合吸附剂,建立了低温情况下吸附材料的吸湿性能测试系统,并进行了大量测试,给出了多种材料在-5℃、-10℃、-15℃下的吸湿量及吸湿速率变化,实验结果表明复合吸附剂的吸附性能与单纯的分子筛相比有了明显的改善,13X型分子筛浸渍浓度20%的NaBr溶液所得试样吸湿量和吸湿速率性能优越,复合过程中损失较少,成本低,可作为复合吸附剂应用于冷库除湿系统中。

References

[1]  National Agricultural Statistics Service (NASS), United States Department of Agriculture (USDA). Capacity of Refrigerated Warehouses 2007 Summary[M]. 2008.
[2]  Kazachki G. Project Progress Meeting in Discussion of Display Case Warm Liquid Defrosting Tests at EPA[M]. Raleigh, NC, 2001.
[3]  Domitrovic R E. Private Conversation with Wesley Hatmaker, a Maintenance Engineer of a Supermarket Refrigeration System, on Saturated Vapor Defrosting Systems[M]. 1999.
[4]  Zhu Xingwang(朱兴旺), Shi Bai(时白), Bai Bao'an(白宝安), et al. Research on energy saving of the parallel unit with several compressor in the refrigerated display cabinet [J]. Fluid Machinery (流体机械), 2005, 33(7): 1-4.
[5]  Sanders C T. The influence of frost formation and defrosting on the performance of air coolers[D]. Netherlands:Netherlands Hogeschool, 1974.
[6]  Niederer D H. Frost and defrosting effects on coil heat transfer [J]. ASHRAE Transactions, 1976, 82(1): 467-473.
[7]  Stoecker W G F, Lux Jr J J, Kooy R J. Energy considerations in hot-gas defrosting of industrial refrigeration coils [J]. ASHRAE Transactions, 1983, 89: 549-573.
[8]  Hewitt N, Huang M J. Defrost cycle performance for a circular shape evaporator air source heat pump [J]. International Journal of Refrigeration, 2008, 31(3): 444-452.
[9]  Huang D, Li Q, Yuan X. Comparison between hot-gas bypass defrosting and reverse-cycle defrosting methods on an air-to-water heat pump [J]. Applied Energy, 2009, 86(9): 1697-1703.
[10]  Wu Jian(吴键), Li Xiaole(李笑乐), Han Baoqi(韩宝琦), Wang Yuqing(王育清). Analysis and experimental study of a zeolite molecular sieve refrigeration cycle [J]. Journal of Engineering Thermophysics(工程热物理学报), 1985, 6(4): 308-310.
[11]  Zhao Zhaohui(赵朝晖), Zhu Dongsheng(朱冬生), Zheng Cheng(郑成). Experimental research on an composite adsorbent of CaCl2-Zeolite 13X [J]. Guangzhou Chemical Industry(广州化工), 2005, 33(3): 25-27.
[12]  Xiao Yonghou(肖永厚), Tao Weichuan(陶伟川), Wang Yangdong(王仰东), Liu Su(刘苏). Adsorption equilibrium and diffusion of water vapor on 13X/CaCl2 composite adsorbents [J]. Natural Gas Chemical Industry(天然气化工), 2010, 35(2): 28-31.
[13]  Wang Guoging(王国庆), Lin Yong(林勇), Wu Feng(吴锋), Chen Shi(陈实). Preparation of composite adsorbent for adsorption refrigeration by soaking in solution [J]. Transactions of Beijing Institute of Technology(北京理工大学学报), 2005, 25(10): 919-921.
[14]  Aristov Y I, Tokarev M M, Cacciola G. Selective water sorbents for multiple applications (1): CaCl2 confined in mesopores of silica gel: Sorption properties [J]. Reaction Kinetics and Catalysis Letters, 1996, 59(2): 325-333.
[15]  Aristov Y I, Tokarev M M, Cacciola G. Selective water sorbents for multiple applications(2): CaCl2 confined in micropores of silica gel: Sorption properties [J]. Reaction Kinetics and Catalysis Letters, 1996, 59(2): 335-342.