%0 Journal Article %T 500 kV高压线路并联电抗器补偿及仿真分析 %A 邵玉槐 %A 高亮 %A 齐锋光 %J - %D 2005 %X 当电力系统低谷负荷时,500 kV线路容性功率使电压升高至550 kV.提出在线路一侧加装并联电抗器补偿无功功率,通过计算线路的潮流和电压以确定电抗器容量,然后用ETAP PowerStation软件对补偿效果进行仿真,仿真结果证实了该方案的可行性.;When power systems operate in light load, the voltage of 500 kV transmission could be promoted to 550 kV by charging capacitive power.This paper suggests that the shunt reactor should be installed at the end of transmission to compensate for reactive power.By calculating the voltage of transmission and load flow, the capacity of the reactor could be determined.Software of ETAP Power Station could be used to simulate effectiveness on compensation.Simulation results are presented to verify the effectiveness of compensation strategy %U http://shdlxyxb.ijournals.cn/ch/reader/view_abstract.aspx?file_no=20050404&flag=1