%0 Journal Article %T Algoritmo Neuro-Difuso para la Detecci¨®n y Clasificaci¨®n de Fallas en L¨ªneas de Transmisi¨®n El¨¦ctrica Usando ANFIS. %A Jhon A. Calder¨®n %A Germ¨¢n Zapata M. %A Demetrio A. Ovalle C. %J Avances en Sistemas e Inform¨¢tica %D 2007 %I %X The detection and classification of faults in electric transmission lines is an essential task to be performed. Within an electric power system a diversity of faults which come from low impedance faults (LIFs) to high impedance faults (HIFs) are exhibited. Last faults are more difficult to be detected due to the use of conventional distance relays. In addition, when they are not detected irreversible consequences are presented into the system. From above, it is inferred that taking into account that HIFs are less frequent than LIFs it appears essential to guaranty that any protection device must be able to satisfactorily detect both kind of electric faults. The aim of this paper is to present an algorithm to detect and classify both kind of faults LIFs and HIFs using ANFIS (Adaptive Network-based Fuzzy Inference System). The inputs for ANFIS are based on RMS (Root-Mean-Square) values from 3-phase and zero-sequence current. The obtained results show that an ANFIS model can detect and classify faults in a precise way including (LIFs y HIFs) in between a half cycle time. %K Fuzzy Neural Algorithm %K Faults Detection and Classification: LIFs %K HIFs %K ANFIS (Adaptive Network-based Fuzzy Inference System) %U http://pisis.unalmed.edu.co/avances/archivos/ediciones/Edicion%20Avances%202007%201/13.pdf