%0 Journal Article %T Criterios microbiol車gicos y de muestreo establecidos en la legislaci車n vigente para el control de Legionella Microbiological and sampling criteria established in the present Spanish legislation for the control of Legionella %A Isabel Inza Rojas %J Revista de Salud Ambiental %D 2006 %I %X Se ha investigado retrospectivamente la relaci車n existente entre las bacterias aerobias totales (BAT) y la presencia de Legionella en un total de 576 muestras de agua procedentes de torres de refrigeraci車n industriales. Los resultados revelan un menor porcentaje de muestras positivas para Legionella (19,8%) por encima del nivel de 104 UFC/ml BAT establecido como l赤mite de acci車n, que por debajo de este (80,2%), lo que indica que este limite no cumple su funci車n en las instalaciones investigadas. Niveles de BAT superiores 100 y 1000 UFC/ml parecen ser m芍s 迆tiles para predecir la presencia de Legionella. Hemos observado una concentraci車n de BAT significativamente m芍s elevada en las muestras positivas para Legionella que en las negativas. Esto indica que las BAT son una buena herramienta para la validaci車n de la eficacia del Plan de Autocontol (PA) establecido en estas instalaciones. Estos resultados apoyan la importancia de seguir manteniendo el control de las BAT (a 36 ㊣ 1 oC) como un indicador de riego de presencia de Legionella y evidencian la necesidad de introducir un l赤mite de acci車n m芍s bajo para las BAT. Por otra parte se discuten algunos aspectos vinculados a la toma de muestras y a su transporte, y algunos t車picos vinculados al periodo de incubaci車n de la enfermedad y a los m谷todos de tipado epidemiol車gico. We have retrospectively investigated the relationship between the presence of total aerobic bacteria (TAB) and the presence of Legionella sp. in 576 water samples from industrial cooling towers. A lower percentage of positive samples for Legionella sp. (19.8%) was encountered when the concentration of TAB was above 104 CFU/ml than below this concentration (80.2%). The concentration of 104 CFU/ml TAB is established in Spanish legislation as the action limit, above which a higher risk of Legionella positive samples is expected. Despite that, our results indicate that levels of TAB above 100 or 1000 CFU/ml seem more useful for predicting the presence of Legionella in the cooling towers investigated. We observed that the concentration of TAB was significatively higher in the positive samples for Legionella than in the negative ones, which seems to indicate that TAB is a good tool for evaluating the effectiveness of the Autocontrol Safety Measures of those cooling towers. Our results reinforce the need for controlling the levels of TAB (at 36 ㊣ 1 oC) because it is a good indicator of the presence of Legionella spp. despite the fact that the standard established as the action limit should be lowered. Within the study we also reviewed the sampling p %K bacterias aerobias totales %K Legionella %K APPCC %K AFLP %K PFGE %K MLST %U http://ojs.easyapps.es/index.php/rsa/article/view/302